Start
Search for Capacity/Type
Semi-hermetic compressors>
Semi-hermetic units>
Open type compressors>
Former types>
BOCKshop
Settings

UL-HGX24e

Types HP (motor code) 1) kW 2) Displacement at 60 Hz (1740 rpm) cfh
UL-HGX24e/145 ML 7 CO2 LT 7 5.5 537.0
UL-HGX24e/145 S 9 CO2 LT 9 5.5 537.0

Certified by Underwriters Laboratories
    Certified by Underwriters Laboratories The U.S. company Underwriters Laboratories Inc. (UL) is a nationally recognized test laboratory by the U.S. federal agency OSHA (Occupational Safety and Health Administration) that tests products and components for safety in accordance with the relevant standards. The awarding of a UL test mark is generally necessary for the North American market in order to be able to market and use technical products such as compressors.
UL-HG CO2 and UL-HG CO2 LT compressors, subcritical
    The compressors are used in both cascade and booster UL-CO2 systems in applications for supermarkets, commercial and industrial cooling systems.
UL-HG CO2
  • Gas-cooled, semi-hermetic reciprocating compressors
  • Subcritical UL-CO2 operating conditions (deep freezing)
  • Operating pressures of up to 51 bar (tc = 15 °C)
  • Conceived for subcritical UL-CO2 systems:
      Standstill pressures LP 40 bar (UL-HGX44e CO2: 30 bar) / HP 55 bar
  • High efficiency in deep freeze applications (to < -15 °C)
UL-HG CO2 LT
  • Gas-cooled, semi-hermetic reciprocating compressors
  • Subcritical UL-CO2 operating conditions (deep freezing)
  • Operating pressures of up to 64 bar (tc = 25 °C)
  • Two motor version (ML and S) for wide frequency range and operation on higher condensing temperatures
  • Conceived for subcritical UL-CO2 systems with high stand still pressures: Standstill pressures LP 100 bar / HP 100 bar
  • High efficiency in deep freeze applications (to < 0 °C)
Special features
  • High compressor efficiency for lowest operating costs
  • Long-life compressor design
  • Broad limits of application and large frequency range for a wide variety of uses
  • Reliable and safe oil supply through pump lubrication
  • Good operating characteristics with low vibration, pulsations, and low operating noise
  • Pressure relief valves for the suction and pressure area
Important information
  • Bock has been involved with CO2 compressor technology since 1993
  • CO2 applications require new system technology and control
  • CO2 applications are not a general solution for substituting F-gases
  • The notes on handling CO2 compressors in the installation instructions must be followed
  • All information is based on current knowledge and may change at any time due to further development of the technology

1)
The motor code describes the compressor motor size based on the HP (Horse Power) of the compressor that is usual in refrigeration technology worldwide. However, the motor code does not correspond to the converted nominal power of the motor from [kW] to [HP].

2)
Nominal power of the motor in [kW].