Technical data
UL-HGX12/20 SH 3 CO2 T
Application | Refrigeration & AC |
Compressor refrigeration capacity | 6.55 kW |
Power consumption | 2.56 kW |
Current draw (460 V) | 5.51 A 1) |
Mass flow | 0.045 kg/s |
at following operating condition:
Refrigerant | R744 |
Reference temperature | Dew point |
Evaporating temperature | 5.1 °C |
High pressure (abs.) | 90.00 bar |
Gas cooler outlet temperature | 35.0 °C |
Supply frequency | 60 Hz |
Voltage | 460 V |
Suction gas superheat | 10 K |
Subcooling (outside cond.) | -- K |
Number of cylinders / Bore / Stroke | 2 / 1.10 inch / 0.63 inch |
Displacement 60 Hz (1740 rpm) | 73 cfh |
Voltage 2) | 265-290V Δ / 440-480V Y -3- 60Hz |
Max. working current 3) | 10.7 / 6.2 A |
Max. power consumption 3) | 3.7 kW |
Starting current (rotor blocked) 3) | 111.0 / 64.0 A |
Motor protection | INT69 G |
Protection terminal box | IP 66 |
Weight | 206 lb |
Frequency range 4) | 30 -70 Hz |
Max. permissible overpressure (g) (LP/HP) 5) | 1450 / 2176 psi |
Connection suction line SV | 7/8 " |
Connection discharge line DV | 3/4 " |
Lubrication | Oil pump |
Oil type R744 | Bock C 170 E |
Oil charge | 46 fl.oz |
Dimensions
Length / Width / Height | 19.69 / 11.54 / 13.01 inch |
Sound pressure level LpA | < 70 dB(A) |
Scope of supply
Semi-hermetic two cylinder reciprocating compressor with
drive motor
Single-section compressor housing with hermetically integrated
electric motor
Winding protection with PTC resistor sensors and
electronic trigger unit INT69 G
115-230 V AC, 50/60 Hz,
IP00
Oil pump
Pressure relief valve suction and discharge line
Oil sump heater 110-120 V -1- 60 Hz, 80 W
Oil charge:
BOCK C 170 E
Sight glass
Suction and discharge connection using blind flange
Inert gas charge
Accessories
Compressor oil PAG (factory filling) 6)
Compressor oil Bock C 170 E as 1 liter refill unit
7)
Hot gas temperature sensor (Pt1000, for external
evaluation)
Steel terminal box
Thermal protection thermostat
Oil temperature sensor (Pt1000, for external evaluation)
Discharge shut-off valve with cutting ring connection for
steel pipes 8)
Suction and discharge line valve in soldering / welding
design
4 anti-vibration pads enclosed
Special voltage and/or frequency (on request)
Notes
1) | Value calculated. Deviation to reality possible. |
2) | Tolerance (± 10%)
relates to the mean value of the voltage range. Other voltages and current types
on request
All data are based on voltage rms values |
3) | - The stated value for the max. power consumption is valid
for the adjusted power supply.
- Starting current (rotor blocked):
- Part winding (PW) motors: Winding 1 / Winding 1+2
- Delta/Star (Δ/Y) motors: Δ / Y
- Take account of the max.
operating current / max. power consumption for designing motor contractors, feed
lines, fuses and motor protection switches. Motor contractors: Consumption
category AC3. |
4) | The maximum permissible working current of the compressor
(Imax) must not be exceeded. Take account of the guidelines for use of frequency
inverter (see compressor assembly instruction or selection software).
|
5) | LP = Low
pressure HP = High pressure |
6) | On request |
7) | Enclosure |
8) | Ø 18 mm |