Technical data
UL-HGX44e/565 S 31 CO2
Application | Refrigeration & AC |
Compressor refrigeration capacity | 107.00 kW |
Power consumption | 24.60 kW |
Current draw (460 V) | 39.20 A 1) |
Mass flow | 0.413 kg/s |
at following operating condition:
Refrigerant | R744 |
Reference temperature | Dew point |
Evaporating temperature | -35.0 °C |
Condensing temperature | -5.0 °C |
Supply frequency | 60 Hz |
Voltage | 460 V |
Suction gas superheat | 10 K |
Subcooling (outside cond.) | 0 K |
Number of cylinders / Bore / Stroke | 4 / 2.36 inch / 1.97 inch |
Displacement 60 Hz (1740 rpm) | 2085 cfh |
Voltage 2) | 440-480V Y/YY -3- 60Hz PW |
Winding divided into | 50% / 50% |
Max. working current 3) | 56.3 A |
Max. power consumption 3) | 40.6 kW |
Starting current (rotor blocked) 3) | 170.0 / 275.0 A |
Motor protection | INT69 G |
Protection terminal box | IP 66 |
Weight | 442 lb |
Frequency range 4) | 25 -70 Hz |
Max. permissible overpressure (g) (LP/HP) 5) | 435 / 798 psi |
Connection suction line SV | 1 3/8 " |
Connection discharge line DV | 1 1/8 " |
Lubrication | Oil pump |
Oil type R744 | BOCKlub E85 |
Oil charge | 102 fl.oz |
Dimensions
Length / Width / Height | 27,6 / 14,21 / 16,02 inch |
Sound power level LWA 6) | 77 db(A) @ -35 °C / -5 °C / 10 K |
| 82 db(A) @ -35 °C / 15 °C / 10 K |
Sound pressure level LpA 6) | 64 db(A) @ -35 °C / -5 °C / 10 K |
| 69 db(A) @ -35 °C / 15 °C / 10 K |
Scope of supply
Semi-hermetic four-cylinder reciprocating compressor
with drive motor
Single-section compressor housing with hermetically integrated electric motor
Rear bearing flange prepared for oil differential pressure
sensor DELTA-P II
Winding protection with PTC resistor sensors and
electronic trigger unit INT69 G
115-230 V AC, 50/60 Hz,
IP00
Oil pump
Pressure relief valve suction and discharge line
Possibility of
connection of oil level controllers ESK, AC+R or CARLY
Possibility of connection of oil level controllers Traxoil 7)
Oil charge:
BOCKlub E85
Sight glass
Internal pressure relief valve
Connection piece suction and discharge line valve in
soldering / welding design
Suction and discharge line valve
Intermediate adapter for discharge line
valve
Inert gas charge
Accessories
Compressor oil BOCKlub E85 as 1 liter refill
unit 8)
Oil sump heater 230 V AC - 1 - 50/60 Hz, 160 W
Oil differential pressure sensor DELTA-P II 115-230 V - 1
- 50/60 Hz 9)
Thermal protection thermostat
Oil temperature sensor (Pt1000, for external evaluation)
8)
4 anti-vibration pads enclosed
Special voltage and/or frequency (on request)
Notes
1) | Value calculated. Deviation to reality possible. |
2) | Tolerance (± 10%)
relates to the mean value of the voltage range. Other voltages and current types
on request
All data are based on voltage rms values |
3) | - The stated value for the max. power consumption is valid
for the adjusted power supply.
- Starting current (rotor blocked):
- Part winding (PW) motors: Winding 1 / Winding 1+2
- Delta/Star (Δ/Y) motors: Δ / Y
- Take account of the max.
operating current / max. power consumption for designing motor contractors, feed
lines, fuses and motor protection switches. Motor contractors: Consumption
category AC3. |
4) | The maximum permissible working current of the compressor
(Imax) must not be exceeded. Take account of the guidelines for use of frequency
inverter (see compressor assembly instruction or selection software).
|
5) | LP = Low
pressure HP = High pressure |
6) | Declared dual-number noise emission values are in
accordance with ISO 4871. The corresponding uncertainty to the sound power level
is KWA = 2,5 dB and to the sound pressure level is KpA =
2,5 dB. The values are valid for 50 Hz with the refrigerant R744 at the standard
rating points according to EN 12900.
- A-weighted sound power level LWA (re 1 pW), in decibel. To
determine the values, measurement methods of the ISO 3740 standard with
accuracy class 2 or higher were used.
- A-weighted sound pressure level LpA (re 20 µPa), in decibel.
The values are calculated from the sound power level in accordance with ISO
11203: LpA = LWA - Q2 at a distance of d = 1m
to the reference box.
|
7) | Only with additional
adapter possible |
8) | Enclosure |
9) | Enclosure (screw-in part mounted) |