Technical data
UL-HGX34e/255 S 12 CO2
| Application | Refrigeration & AC |
| Compressor refrigeration capacity | 47.30 kW |
| Power consumption | 11.20 kW |
| Current draw (460 V) | 17.00 A 1) |
| Mass flow | 0.183 kg/s |
at following operating condition:
| Refrigerant | R744 |
| Reference temperature | Dew point |
| Evaporating temperature | -35.0 °C |
| Condensing temperature | -5.0 °C |
| Supply frequency | 60 Hz |
| Voltage | 460 V |
| Suction gas superheat | 10 K |
| Subcooling (outside cond.) | 0 K |
| Number of cylinders / Bore / Stroke | 4 / 2.17 inch / 1.06 inch |
| Displacement 60 Hz (1740 rpm) | 946 cfh |
| Voltage 2) | 265-290V Δ / 440-480V Y -3- 60Hz |
| Max. working current 3) | 44.8 / 25.9 A |
| Max. power consumption 3) | 19.1 kW |
| Starting current (rotor blocked) 3) | 178.0 / 103.0 A |
| Motor protection | INT69 G |
| Protection terminal box | IP 66 |
| Weight | 231 lb |
| Frequency range 4) | 25 -70 Hz |
| Max. permissible overpressure (g) (LP/HP) 5) | 435 / 798 psi |
| Connection suction line SV | 1 1/8 " |
| Connection discharge line DV | 7/8 " |
| Lubrication | Oil pump |
| Oil type R744 | BOCKlub E85 |
| Oil charge | 46 fl.oz |
| Dimensions
Length / Width / Height | 22.52 / 12.52 / 12.52 inch |
| Sound power level LWA 6) | 72 db(A) @ -35 °C / -5 °C / 10 K |
| 76 db(A) @ -35 °C / 15 °C / 10 K |
| Sound pressure level LpA 6) | 60 db(A) @ -35 °C / -5 °C / 10 K |
| 63 db(A) @ -35 °C / 15 °C / 10 K |
Scope of supply
Semi-hermetic four
cylinder reciprocating compressor with drive motor
Single-section compressor housing with hermetically integrated electric
motor
Winding protection with PTC resistor sensors and
electronic trigger unit INT69 G
115-230 V AC, 50/60 Hz,
IP00
Oil pump
Pressure relief valve suction and discharge line
Possibility of
connection of oil level controllers ESK, Traxoil, AC+R or CARLY 7)
Oil charge:
BOCKlub E85
Sight glass
Suction and discharge line valve in soldering / welding
design
Inert gas charge
Notes
| 1) | Value calculated. Deviation to reality possible. |
| 2) | Tolerance (± 10%)
relates to the mean value of the voltage range. Other voltages and current types
on request
All data are based on voltage rms values |
| 3) | - The stated value for the max. power consumption is valid
for the adjusted power supply.
- Starting current (rotor blocked):
- Part winding (PW) motors: Winding 1 / Winding 1+2
- Delta/Star (Δ/Y) motors: Δ / Y
- Take account of the max.
operating current / max. power consumption for designing motor contractors, feed
lines, fuses and motor protection switches. Motor contractors: Consumption
category AC3. |
| 4) | The maximum permissible working current of the compressor
(Imax) must not be exceeded. Take account of the guidelines for use of frequency
inverter (see compressor assembly instruction or selection software).
|
| 5) | LP = Low
pressure HP = High pressure |
| 6) | Declared dual-number noise emission values are in
accordance with ISO 4871. The corresponding uncertainty to the sound power level
is KWA = 2,5 dB and to the sound pressure level is KpA =
2,5 dB. The values are valid for 50 Hz with the refrigerant R744 at the standard
rating points according to EN 12900.
- A-weighted sound power level LWA (re 1 pW), in decibel. To
determine the values, measurement methods of the ISO 3740 standard with
accuracy class 2 or higher were used.
- A-weighted sound pressure level LpA (re 20 µPa), in decibel.
The values are calculated from the sound power level in accordance with ISO
11203: LpA = LWA - Q2 at a distance of d = 1m
to the reference box.
|
| 7) | Only with additional