Technical data
UL-HGX12P/110 ML 2
| Application | Refrigeration & AC |
| Compressor refrigeration capacity | 5.61 kW |
| Power consumption | 1.92 kW |
| Current draw (460 V) | 3.37 A 1) |
| Mass flow | 0.039 kg/s |
at following operating condition:
| Refrigerant | R134a |
| Reference temperature | Dew point |
| Evaporating temperature | 5.0 °C |
| Condensing temperature | 50.0 °C |
| Supply frequency | 60 Hz |
| Voltage | 460 V |
| Suction gas temperature | 20 °C |
| Subcooling (outside cond.) | 0 K |
| Number of cylinders / Bore / Stroke | 2 / 1.77 inch / 1.34 inch |
| Displacement 60 Hz (1740 rpm) | 399 cfh |
| Voltage 2) | 265-290V Δ / 440-480V Y -3- 60Hz |
| Max. working current 3) | 9.2 / 5.3 A |
| Max. power consumption 3) | 3.8 kW |
| Starting current (rotor blocked) 3) | 43.0 / 25.0 A |
| Motor protection | INT69 G |
| Protection terminal box | IP 66 |
| Weight | 104 lb |
| Frequency range 4) | 30 -70 Hz |
| Max. permissible overpressure (g) (LP/HP) 5) | 276 / 406 psi |
| Connection suction line SV | 16 mm - 5/8 " |
| Connection discharge line DV | 12 mm - 1/2 " |
| Lubrication | Oil pump |
| Oil type R134a, R404A, R407A/C/F, R448A, R449A, R450A, R513A | BOCKlub E55 |
| Oil charge | 28 fl.oz |
| Dimensions
Length / Width / Height | 412 / 223 / 280 mm |
Scope of supply
Semi-hermetic two cylinder reciprocating compressor with
drive motor
Single-section compressor housing with hermetically integrated
electric motor
Winding protection with PTC resistor sensors and
electronic trigger unit INT69 G
115-230 V AC, 50/60 Hz,
IP00
Oil pump
Possibility for connection of oil pressure safety switch
MP55
Possibility of
connection of oil level controllers ESK, Traxoil, AC+R or CARLY 6)
Oil charge:
BOCKlub E55
Sight glass
Suction and discharge line valve
Inert gas charge
Notes
| 1) | Value calculated. Deviation to reality possible. |
| 2) | Tolerance (± 10%)
relates to the mean value of the voltage range. Other voltages and current types
on request
All data are based on voltage rms values |
| 3) | - The stated value for the max. power consumption is valid
for the adjusted power supply.
- Starting current (rotor blocked):
- Part winding (PW) motors: Winding 1 / Winding 1+2
- Delta/Star (Δ/Y) motors: Δ / Y
- Take account of the max.
operating current / max. power consumption for designing motor contractors, feed
lines, fuses and motor protection switches. Motor contractors: Consumption
category AC3. |
| 4) | The maximum permissible working current of the compressor
(Imax) must not be exceeded. Take account of the guidelines for use of frequency
inverter (see compressor assembly instruction or selection software).
|
| 5) | LP = Low
pressure HP = High pressure |
| 6) | Only with additional
adapter possible |