Technical data
SHGX34e/380-4 SPB
Application | Refrigeration & AC |
Compressor refrigeration capacity | 19.00 kW |
Power consumption | 6.01 kW 1) |
Current draw (400 V) | 9.75 A |
Mass flow | 0.124 kg/s |
at following operating condition:
Refrigerant | R134a |
Reference temperature | Dew point |
Evaporating temperature | 5.0 °C |
Condensing temperature | 46.5 °C |
Air inlet temperature | 32.0 °C |
Supply frequency | 50 Hz |
Voltage | 400 V |
Suction gas temperature | 20 °C |
Subcooling (outside cond.) | 3 K |
Number of cylinders / Bore / Stroke | 4 / 55 mm / 40 mm |
Displacement 50 Hz (1450 ¹/min) | 33,10 m³/h |
Voltage 2) | 220-240V Δ / 380-420V Y -3- 50Hz |
Max. working current 3) | 31.2 / 18.0 A |
Max. power consumption 3) | 11.1 kW |
Starting current (rotor blocked) 3) | 132.0 / 76.0 A |
Motor protection | INT69 G |
Protection terminal box | IP 66 |
Weight | 231 kg |
Frequency range 4) | 25 - 70 Hz |
Max. permissible overpressure (g) (LP/HP) 5) | 19 / 28 bar |
Connection suction line SV | 35 mm - 1 3/8 " |
Connection discharge line DV | 16 mm - 5/8 " |
Connection liqiud outlet line FLA | 16 mm - 5/8 " |
Connection liqiud outlet line FLE | 16 mm - 5/8 " |
Lubrication | Oil pump |
Oil type R134a, R404A, R407A/C/F, R448A, R449A, R450A, R513A | BOCKlub E55 |
Oil type R22 | BOCKlub A46 |
Oil charge | 1,3 Ltr. |
Dimensions
Length / Width / Height | 1570 / 679 / 968 mm |
Number fan motors | 1 |
Voltage | 230 V - 1 - 50 Hz |
Max. working current 50 Hz | 1 x 2,60 A |
Max. power consumption 50 Hz | 1 x 600 W |
Air flow 50 Hz | 7020 m³/h |
Receiver content | 10,0 Ltr. |
Volume condenser | 8,9 Ltr. |
Scope of supply
Level 1: Plug & Play
- Bock semi-hermetic compressor
- Generously sized condenser for all climate zones
- AC fan
- Liquid receiver
- Weatherproofed powder coated steel sheets enclosure
- Compressor located in acoustically lined enclosure
- Main isolator- Complete liquid - and suction pipework arrangements
- Electric cabinet and electrical wiring of all components
- Fan speed controller
- High pressure safety limiter + controller/ +low pressure controller
- Oil sump heater
- Oil pressure safety switch 6)
Level 2:
- Level 1
- Oil separator 6)
Level 3:
- Level 2
- Stepless compressor speed control via Danfoss VSD (frequency converter) 6)
Accessories
Safety valve for receiver 7)
Further accessory parts see compressor 7)
Notes
1) | Power consumption of condenser fans included.
|
2) | Tolerance (± 10%)
relates to the mean value of the voltage range. Other voltages and current types
on request
All data are based on voltage rms values |
3) | - The stated value for the max. power consumption is valid
for the adjusted power supply.
- Starting current (rotor blocked):
- Part winding (PW) motors: Winding 1 / Winding 1+2
- Delta/Star (Δ/Y) motors: Δ / Y
- Take account of the max.
operating current / max. power consumption for designing motor contractors, feed
lines, fuses and motor protection switches. Motor contractors: Consumption
category AC3. |
4) | The maximum permissible working current of the compressor
(Imax) must not be exceeded. Take account of the guidelines for use of frequency
inverter (see compressor assembly instruction or selection software).
|
5) | LP = Low
pressure HP = High pressure |
6) | Mounted |
7) | Enclosure |