|
| |
| | |
| | |
|
| Scope of supply and accessories |
|
| Scope of supply and accessories |
|
|
| Dimensions and connections |
|
| Dimensions and connections |
|
| | |
|
| Spare part list, drawings & downloads |
|
| Spare part list, drawings & downloads |
|
| | |
|
|
| |
| |
|
|
Unlimited application range
Supplementary cooling or reduced suction gas temperature (Δtoh<20K)
Compressor operation is possible within the limits shown
on the diagrams of application. Please note the coloured areas. Compressor
application limits should not be chosen for design purposes or continuous
operation. Axis values refer to dew point (saturated vapour line).
|
Number of cylinders / Bore / Stroke |
4 / 55 mm / 40 mm |
|
Displacement 50 Hz (1450 ¹/min) |
33,10 m³/h |
|
Voltage |
220-240V Δ / 380-420V Y -3- 50Hz |
|
Max. working current |
31.2 / 18.0 A |
|
Max. power consumption |
11.1 kW |
|
Starting current (rotor blocked) |
132.0 / 76.0 A |
|
Motor protection |
INT69 G |
|
Protection terminal box |
IP 66 |
|
Weight |
231 kg |
|
Frequency range |
25 - 70 Hz |
|
Max. permissible overpressure (g) (LP/HP) |
19 / 28 bar |
|
Connection suction line SV |
35 mm - 1 3/8 " |
|
Connection discharge line DV |
16 mm - 5/8 " |
|
Connection liqiud outlet line FLA |
16 mm - 5/8 " |
|
Connection liqiud outlet line FLE |
16 mm - 5/8 " |
|
Lubrication |
Oil pump |
|
Oil type R134a, R404A, R407A/C/F, R448A, R449A, R450A, R513A |
BOCKlub E55 |
|
Oil type R22 |
BOCKlub A46 |
|
Oil charge |
1,3 Ltr. |
|
Dimensions
Length / Width / Height |
1570 / 679 / 968 mm |
|
Number fan motors |
1 |
|
Voltage |
230 V - 1 - 50 Hz |
|
Max. working current 50 Hz |
1 x 2,60 A |
|
Max. power consumption 50 Hz |
1 x 600 W |
|
Air flow 50 Hz |
7020 m³/h |
|
Receiver content |
10,0 Ltr. |
|
Volume condenser |
8,9 Ltr. |
Level 1: Plug & Play - Bock semi-hermetic compressor - Generously sized condenser for all climate zones - AC fan - Liquid receiver - Weatherproofed powder coated steel sheets enclosure - Compressor located in acoustically lined enclosure - Main isolator- Complete liquid - and suction pipework arrangements - Electric cabinet and electrical wiring of all components - Fan speed controller - High pressure safety limiter + controller/ +low pressure controller - Oil sump heater - Oil pressure safety switch |
Level 2: - Level 1 - Oil separator |
Level 3: - Level 2 - Stepless compressor speed control via Danfoss VSD (frequency converter) |
| Dimensioned drawing | display with dimensions and connections |
Format: PDF |
Download |
|
| SV |
Suction line valve, tube ø |
35 mm - 1 3/8 " |
| DV |
Discharge line valve, tube ø |
16 mm - 5/8 " |
| A |
Connection suction side, not lockable |
7/16" UNF |
| B |
Connection discharge side, not lockable |
7/16" UNF |
| FLA |
Liquid outlet, tube ø |
16 mm - 5/8 " |
| FLE |
Liquid inlet, tube ø |
16 mm - 5/8 " |
| SI |
Connection safety valve |
1/2" NPTF |
| Y1 |
Connection liquid side, lockable |
7/16" UNF |
| Y2 |
Connection liquid side, not lockable |
7/16" UNF |
| Y3 |
Connection for Schrader valve speed control for the fan |
7/16" UNF |
| Confirm the license rules | |
|
|
| |
|
|
Technical dataSHGX34e/380-4 SPB | Application | Refrigeration & AC | | Compressor refrigeration capacity | 19.00 kW | | Power consumption | 6.01 kW 1) | | Current draw (400 V) | 9.75 A | | Mass flow | 0.124 kg/s |
at following operating condition: | Refrigerant | R134a | | Reference temperature | Dew point | | Evaporating temperature | 5.0 °C | | Condensing temperature | 46.5 °C | | Air inlet temperature | 32.0 °C | | Supply frequency | 50 Hz | | Voltage | 400 V | | Suction gas temperature | 20 °C | | Subcooling (outside cond.) | 3 K |
| Number of cylinders / Bore / Stroke | 4 / 55 mm / 40 mm | | Displacement 50 Hz (1450 ¹/min) | 33,10 m³/h | | Voltage 2) | 220-240V Δ / 380-420V Y -3- 50Hz | | Max. working current 3) | 31.2 / 18.0 A | | Max. power consumption 3) | 11.1 kW | | Starting current (rotor blocked) 3) | 132.0 / 76.0 A | | Motor protection | INT69 G | | Protection terminal box | IP 66 | | Weight | 231 kg | | Frequency range 4) | 25 - 70 Hz | | Max. permissible overpressure (g) (LP/HP) 5) | 19 / 28 bar | | Connection suction line SV | 35 mm - 1 3/8 " | | Connection discharge line DV | 16 mm - 5/8 " | | Connection liqiud outlet line FLA | 16 mm - 5/8 " | | Connection liqiud outlet line FLE | 16 mm - 5/8 " | | Lubrication | Oil pump | | Oil type R134a, R404A, R407A/C/F, R448A, R449A, R450A, R513A | BOCKlub E55 | | Oil type R22 | BOCKlub A46 | | Oil charge | 1,3 Ltr. | | Dimensions
Length / Width / Height | 1570 / 679 / 968 mm | | Number fan motors | 1 | | Voltage | 230 V - 1 - 50 Hz | | Max. working current 50 Hz | 1 x 2,60 A | | Max. power consumption 50 Hz | 1 x 600 W | | Air flow 50 Hz | 7020 m³/h | | Receiver content | 10,0 Ltr. | | Volume condenser | 8,9 Ltr. |
Scope of supplyLevel 1: Plug & Play - Bock semi-hermetic compressor - Generously sized condenser for all climate zones - AC fan - Liquid receiver - Weatherproofed powder coated steel sheets enclosure - Compressor located in acoustically lined enclosure - Main isolator- Complete liquid - and suction pipework arrangements - Electric cabinet and electrical wiring of all components - Fan speed controller - High pressure safety limiter + controller/ +low pressure controller - Oil sump heater - Oil pressure safety switch 6) Level 2: - Level 1 - Oil separator 6) Level 3: - Level 2 - Stepless compressor speed control via Danfoss VSD (frequency converter) 6) Notes| 1) | Power consumption of condenser fans included.
| | 2) | Tolerance (± 10%)
relates to the mean value of the voltage range. Other voltages and current types
on request
All data are based on voltage rms values | | 3) | - The stated value for the max. power consumption is valid
for the adjusted power supply.
- Starting current (rotor blocked):
- Part winding (PW) motors: Winding 1 / Winding 1+2
- Delta/Star (Δ/Y) motors: Δ / Y
- Take account of the max.
operating current / max. power consumption for designing motor contractors, feed
lines, fuses and motor protection switches. Motor contractors: Consumption
category AC3. | | 4) | The maximum permissible working current of the compressor
(Imax) must not be exceeded. Take account of the guidelines for use of frequency
inverter (see compressor assembly instruction or selection software).
| | 5) | LP = Low
pressure HP = High pressure | | 6) | Mounted |
|