Air-cooled condensation unit with large-dimensioned condensers, optimised
closed loops and heat transfer in conjunction with high-power fans. These
cost-effective fans with thermal protection shield are well-suited for
electronic speed regulation for an optimal condensation pressure
setting.
Semi-hermetic suction gas-cooled reciprocating compressor in
compact design. The best possible serviceability is provided by means of a
replaceable drive motor, among other things. The compressor stands out due to
its outstanding running comfort and efficient operating performance. The suction
shut-off valve can be rotated by 90° in each instance. Dependable mechanism
lubrication is guaranteed by means of an oil pump which is independent of
rotating direction, as well as a large-volume oil sump. An electronic motor
protection uses PTC sensors in series to monitor the winding temperature and, if
desired, the discharge gas temperature.
Colour: blue (RAL
5000)
Technical data
SHGX12P/90-4 SL
Application | Refrigeration & AC |
Compressor refrigeration capacity | 4.90 kW |
Power consumption | 1.82 kW 1) |
Current draw (400 V) | 3.28 A |
Mass flow | 0.030 kg/s |
at following operating condition:
Refrigerant | R134a |
Reference temperature | Dew point |
Evaporating temperature | 5.0 °C |
Condensing temperature | 40.3 °C |
Air inlet temperature | 32.0 °C |
Supply frequency | 50 Hz |
Voltage | 400 V |
Suction gas temperature | 20 °C |
Subcooling (outside cond.) | 3 K |
Number of cylinders / Bore / Stroke | 2 / 41,5 mm / 34 mm |
Displacement 50/60 Hz (1450/1740 ¹/min) | 8,00 / 9,60 m³/h |
Voltage 2) | 220-240V Δ / 380-420V Y -3- 50Hz |
| 265-290V Δ / 440-480V Y -3- 60Hz |
Max. working current 3) | 9.1 / 5.3 A |
Max. power consumption 3) | 3.0 kW |
Starting current (rotor blocked) 3) | 45.0 / 26.0 A |
Motor protection | INT69 G |
Protection terminal box | IP 66 |
Weight | 115 kg |
Frequency range 4) | 30 -70 Hz |
Max. permissible overpressure (g) (LP/HP) 5) | 19 / 28 bar |
Connection suction line SV | 16 mm - 5/8 " |
Connection discharge line DV | 12 mm - 1/2 " |
Connection liqiud outlet line FLA | 12 mm - 1/2 " |
Connection liqiud outlet line FLE | 12 mm - 1/2 " |
Lubrication | Oil pump |
Oil type R134a, R404A, R407A/C/F, R448A, R449A, R450A, R513A | BOCKlub E55 |
Oil type R22 | BOCKlub A46 |
Oil charge | 0,8 Ltr. |
Dimensions
Length / Width / Height | 885 / 650 / 630 mm |
Number fan motors | 1 |
Voltage | 230 V - 1 - 50/60 |
Max. working current 50/60 Hz | 1 x 2,60 / 3,50 A |
Max. power consumption 50/60 Hz | 1 x 550 / 800 W |
Air flow 50/60 Hz | 6300 / 7300 m³/h |
Receiver content | 6.0 Ltr. |
Max. refrigerant charge
R134a 6) | 6,6 kg |
R404A / R507 6) | 5,8 kg |
R407C / R407F 6) | 6,3 / 6,2 kg |
R22 6) | 6,5 kg |
Volume condenser | 3,21 Ltr. |
Sound power level LWA 7) | 77 dB(A) |
Sound pressure level LpA 7) | 63 dB(A) @ 1 m |
| 46 dB(A) @ 10 m |
Scope of supply
HA P or HAX P semi-hermetic motor compressor (Extent of delivery see compressor) installed on the unit with anti-vibration pads. The liquid receivers with sight glass and Rotalock shut-off valve with brazing connection. Tank is provided (appropriate pressure appliance guideline)
Air-cooled finned tube condenser with 1 ventilator:
-
Ventilator 230 V - 1 - 50/60 Hz, with bimetal winding protection, phase control
for speed adjustment (speed regulator not included in scope of supplies)
-
With piping on discharge and liquide side. Service charge
Level 1: Oil sump heater 8)
Level 2: Oil sump heater, high/low pressure switch 8)
Level 3.1: Oil sump heater, high/low pressure switch, oil pressure safety switch 8)
Level 4.1: Oil sump heater, high/low pressure switch, oil pressure safety switch, oil separator 8)
4 rubber plates enclosed for installation of the condensing unit
Accessories
Safety valve for receiver 9)
Speed controll for the ventilator 9)
Further accessory parts see compressor 9)
Notes
1) | Power consumption of condenser fans included.
|
2) | Tolerance (± 10%)
relates to the mean value of the voltage range. Other voltages and current types
on request
All data are based on voltage rms values |
3) | - The stated value for the max. power consumption is valid
for the adjusted power supply.
- Starting current (rotor blocked):
- Part winding (PW) motors: Winding 1 / Winding 1+2
- Delta/Star (Δ/Y) motors: Δ / Y
- Take account of the max.
operating current / max. power consumption for designing motor contractors, feed
lines, fuses and motor protection switches. Motor contractors: Consumption
category AC3. |
4) | The maximum permissible working current of the compressor
(Imax) must not be exceeded. Take account of the guidelines for use of frequency
inverter (see compressor assembly instruction or selection software).
|
5) | LP = Low
pressure HP = High pressure |
6) | With liquide temperature at 20°C and 90 % capacity |
7) | Declared dual-number noise emission values are in
accordance with ISO 4871. The corresponding uncertainty to the sound power level
is KWA = 2,5 dB and to the sound pressure level is KpA =
2,5 dB. The values are valid for 50 Hz.
- A-weighted sound power level LWA (re 1 pW), in decibel. To
determine the values, measurement methods of the ISO 3740 standard with
accuracy class 2 or higher were used.
- A-weighted sound pressure level LpA (re 20 µPa), in decibel.
The values are calculated from the sound power level in accordance with ISO
11203: LpA = LWA - Q2 at a distance of d = 1m
or d = 10 m to the reference box.
|
8) | Mounted |
9) | Enclosure |