Technical data
SHAX44e/665-4 L
Application | Refrigeration & AC |
Compressor refrigeration capacity | 11.40 kW |
Power consumption | 8.69 kW 1) |
Current draw (400 V) | 15.10 A |
Mass flow | 0.079 kg/s |
at following operating condition:
Refrigerant | R404A, R507 |
Reference temperature | Dew point |
Evaporating temperature | -35.0 °C |
Condensing temperature | 36.3 °C |
Air inlet temperature | 32.0 °C |
Supply frequency | 50 Hz |
Voltage | 400 V |
Suction gas temperature | 20 °C |
Subcooling (outside cond.) | 3 K |
Number of cylinders / Bore / Stroke | 4 / 65 mm / 50 mm |
Displacement 50/60 Hz (1450/1740 ¹/min) | 57,70 / 69,30 m³/h |
Voltage 2) | 380-420V Y/YY -3- 50Hz PW |
| 440-480V Y/YY -3- 60Hz PW |
Winding divided into | 50% / 50% |
Max. working current 3) | 20.3 A |
Max. power consumption 3) | 11.0 kW |
Starting current (rotor blocked) 3) | 101.0 / 174.0 A |
Motor protection | INT69 G |
Protection terminal box / HA-fan | IP 66 / IP 44 |
Voltage HA-fan | 230 V - 1 - 50/60 Hz, 140 W |
Weight | 325 kg |
Frequency range 4) | 25 - 70 Hz |
Max. permissible overpressure (g) (LP/HP) 5) | 19 / 28 bar |
Connection suction line SV | 35 mm - 1 3/8 " |
Connection discharge line DV | 22 mm - 7/8 " |
Connection liqiud outlet line FLA | 22 mm - 7/8 " |
Connection liqiud outlet line FLE | 22 mm - 7/8 " |
Lubrication | Oil pump |
Oil type R134a, R404A, R407A/C/F, R448A, R449A, R450A, R513A | BOCKlub E55 |
Oil type R22 | BOCKlub A46 |
Oil charge | 2,7 Ltr. |
Oil sump heater | 230 V - 1 - 50/60 Hz, 160 W |
Dimensions of unit
Length / Width / Height | 1243 / 894 / 1306 mm |
Number fan motors | 4 |
Voltage | 230 V - 1 - 50/60 Hz |
Max. working current 50/60 Hz | 4 x 2,60 / 3,50 A |
Max. power consumption 50/60 Hz | 4 x 550 / 800 W |
Air flow 50/60 Hz | 19700 / 24200 m³/h |
Receiver content | 23.00 Ltr. |
Max. refrigerant charge
R134a 6) | 25,4 kg |
R404A / R507 6) | 22,1 kg |
R407C / R407F 6) | 24,0 / 23,7 kg |
R448A / R449A 6) | 23,0 / 23,1 kg |
R22 6) | 25,0 kg |
Volume condenser | 15,4 Ltr. |
Sound power level LWA 7) | 85 dB(A) |
Sound pressure level LpA 7) | 69 dB(A) @ 1 m |
| 53 dB(A) @ 10 m |
Scope of supply
Rear bearing flange prepared for oil differential pressure
sensor DELTA-P II
HA or HAX semi-hermetic motor compressor (Extent of delivery see compressor) installed with rubber anti-vibration pads on liquide receiver. The liquid receivers with sight glass and Rotalock shut-off valve with brazing connection. Tank is provided (appropriate pressure appliance guideline)
Oil pump
Possibility for connection of oil pressure safety switch
MP54
Air-cooled finned tube condenser with 4
ventilators:
- Ventilators 230 V - 1 - 50/60 Hz, with bimetal winding
protection, phase control for speed adjustment (regulator not included in scope
of supplies)
- With piping on discharge and liquide side. Service charge
4 rubber plates enclosed for installation of the condensing unit
Accessories
Digital capacity regulator DCR14 230 V - 1 - 50/60
Hz, IP65
1 digital capacity regulator = 50% residual capacity
Cylinder cover prepared for digital capacity regulator
Oil sump heater 230 V - 1 - 50/60 Hz, 160
W
Oil pressure safety switch MP54 230 V - 1 - 50/60 Hz,
IP20 8)
Oil differential pressure sensor DELTA-P II 220-240 V -
1 - 50/60 Hz 9)
Thermal protection thermostat per cylinder cover
High pressure safety limiter + controller/ +low pressure
controller 8)
Safety valve for receiver 8)
Oil separator incl. mounting
Larger liquid receiver with 35 l
volume
Special voltage and/or frequency (on request)
Notes
1) | Power consumption of condenser fans included.
|
2) | Tolerance (± 10%)
relates to the mean value of the voltage range. Other voltages and current types
on request
All data are based on voltage rms values
PW = part
winding, motors for part winding starting (no start unloaders required)
Designs for Y/D on request |
3) | - The stated value for the max. power consumption is valid
for the adjusted power supply.
- Starting current (rotor blocked):
- Part winding (PW) motors: Winding 1 / Winding 1+2
- Delta/Star (Δ/Y) motors: Δ / Y
- Take account of the max.
operating current / max. power consumption for designing motor contractors, feed
lines, fuses and motor protection switches. Motor contractors: Consumption
category AC3. |
4) | The maximum permissible working current of the compressor
(Imax) must not be exceeded. Take account of the guidelines for use of frequency
inverter (see compressor assembly instruction or selection software).
|
5) | LP = Low
pressure HP = High pressure |
6) | With liquide temperature at 20°C and 90 % capacity |
7) | Declared dual-number noise emission values are in
accordance with ISO 4871. The corresponding uncertainty to the sound power level
is KWA = 2,5 dB and to the sound pressure level is KpA =
2,5 dB. The values are valid for 50 Hz.
- A-weighted sound power level LWA (re 1 pW), in decibel. To
determine the values, measurement methods of the ISO 3740 standard with
accuracy class 2 or higher were used.
- A-weighted sound pressure level LpA (re 20 µPa), in decibel.
The values are calculated from the sound power level in accordance with ISO
11203: LpA = LWA - Q2 at a distance of d = 1m
or d = 10 m to the reference box.
|
8) | Mounted |