Technical data
HGX34e/380 ML 6 LG
| Application | Refrigeration & AC |
| Compressor refrigeration capacity | 17.40 kW |
| Power consumption | 5.63 kW |
| Current draw (400 V) | 9.62 A |
| Mass flow | 0.122 kg/s |
at following operating condition:
| Refrigerant | R134a |
| Reference temperature | Dew point |
| Evaporating temperature | 5.0 °C |
| Condensing temperature | 50.0 °C |
| Supply frequency | 50 Hz |
| Voltage | 400 V |
| Suction gas temperature | 20 °C |
| Subcooling (outside cond.) | 0 K |
| Number of cylinders / Bore / Stroke | 4 / 55 mm / 40 mm |
| Displacement 50/60 Hz (1450/1740 ¹/min) | 33,10 / 39,70 m³/h |
| Voltage 1) | 220-240V Δ / 380-420V Y -3- 50Hz |
| 265-290V Δ / 440-480V Y -3- 60Hz |
| Max. working current 2) | 26.1 / 15.1 A |
| Max. power consumption 2) | 9.3 kW |
| Starting current (rotor blocked) 2) | 111.0 / 64.0 A |
| Motor protection | INT69 G |
| Protection terminal box | IP 66 |
| Weight | 93 kg |
| Frequency range 3) | 25 - 70 Hz |
| Max. permissible overpressure (g) (LP/HP) 4) | 19 / 32 bar |
| Connection suction line SV | 28 mm - 1 1/8 " |
| Connection discharge line DV | 22 mm - 7/8 " |
| Lubrication | Oil pump |
| Oil type R134a, R404A, R407A/C/F, R448A, R449A, R450A, R513A | BOCKlub E55 |
| Oil type R1234yf, R1234ze, R455A, R454C | BOCKlub E55; to>15 °C: BOCKlub E85 |
| Oil charge | 1,3 Ltr. |
| Dimensions
Length / Width / Height | 535 / 282 / 318 mm |
| Sound power level LWA 5) | 72 dB(A) @ -35 °C / +40 °C |
| 68 dB(A) @ -10 °C / +45 °C |
| Sound pressure level LpA 5) | 59 dB(A) @ -35 °C / +40 °C |
| 55 dB(A) @ -10 °C / +45 °C |
Scope of supply
Semi-hermetic four
cylinder reciprocating compressor with drive motor
Single-section compressor housing with hermetically integrated electric
motor
Oil pump
Winding protection with PTC resistor sensors. Electronic
triggering unit INT69 G to be fitted in switch cupboard (enclosed)
Possibility of
connection of oil level controllers ESK, Traxoil, AC+R or CARLY 6)
Oil charge:
BOCKlub E55
Sight glass
Suction and discharge line valve
Inert gas charge
Accessories
Capacity regulator 230 V - 1 - 50/60 Hz, IP65
1 capacity regulator = 50% residual capacity
Compressor oil BOCKlub E85 (factory filling)
7)
Cylinder cover prepared for capacity regulator
Oil sump heater 230 V - 1 - 50/60 Hz, 160 W
Thermal protection thermostat per cylinder cover
8)
Additional fan
230 V AC - 1 - 50 Hz, 97 W,
IP44
230 V AC - 1 - 60 Hz, 128 W 9)
Step protection
Injection nozzle for liquid injection 9)
4 anti-vibration pads enclosed
Special voltage and/or frequency (on request)
Notes
| 1) | Tolerance (± 10%)
relates to the mean value of the voltage range. Other voltages and current types
on request
All data are based on voltage rms values |
| 2) | - The stated value for the max. power consumption is valid
for the adjusted power supply.
- Starting current (rotor blocked):
- Part winding (PW) motors: Winding 1 / Winding 1+2
- Delta/Star (Δ/Y) motors: Δ / Y
- Take account of the max.
operating current / max. power consumption for designing motor contractors, feed
lines, fuses and motor protection switches. Motor contractors: Consumption
category AC3. |
| 3) | The maximum permissible working current of the compressor
(Imax) must not be exceeded. Take account of the guidelines for use of frequency
inverter (see compressor assembly instruction or selection software).
|
| 4) | LP = Low
pressure HP = High pressure |
| 5) | Declared dual-number noise emission values are in
accordance with ISO 4871. The corresponding uncertainty to the sound power level
is KWA = 2,5 dB and to the sound pressure level is KpA =
2,5 dB. The values are valid for 50 Hz with the refrigerant R404A at the
standard rating points according to EN 12900.
- A-weighted sound power level LWA (re 1 pW), in decibel. To
determine the values, measurement methods of the ISO 3740 standard with
accuracy class 2 or higher were used .
- A-weighted sound pressure level LpA (re 20 µPa), in decibel.
The values are calculated from the sound power level in accordance with ISO
11203: LpA = LWA - Q2 at a distance of d = 1m
to the reference box.
|
| 6) | Only with additional
adapter possible |
| 7) | from to>15°C for R1234yf/R1234ze |
| 8) | Mounted |
| 9) | Enclosure |