Semi-hermetic suction gas-cooled reciprocating compressor in compact design
especially for the use with hydrocarbons. The best possible serviceability is
provided by means of a replaceable drive unit, among other things. The
compressor stands out due to its outstanding running comfort and efficient
operating performance. The suction shut-off valve can be rotated by 90° in each
instance. Dependable mechanism lubrication is guaranteed by means of an oil pump
which is independent of rotating direction, as well as a large-volume oil
sump.
An additional connection facility for an oil level regulator is available as
a standard. The electrical connection is simplified by means of a large-volume
electric terminal box. The electronic motor protection INT69 G (for installation
in the switch cabinet) uses PTC sensors in series to monitor the winding
temperature and optionally the discharge gas temperature. The compressor has to
be equipped with an oil sump heater (accessory).
Colour: blue (RAL 5000)
Technical data
HG66e/2070-4 HC
Application | Refrigeration & AC |
Compressor refrigeration capacity | 80.90 kW |
Power consumption | 31.70 kW |
Current draw (400 V) | 56.30 A |
Mass flow | 0.276 kg/s |
at following operating condition:
Refrigerant | R290 |
Reference temperature | Dew point |
Evaporating temperature | -10.0 °C |
Condensing temperature | 45.0 °C |
Supply frequency | 50 Hz |
Voltage | 400 V |
Suction gas temperature | 20 °C |
Subcooling (outside cond.) | 0 K |
Number of cylinders / Bore / Stroke | 6 / 87 mm / 58 mm |
Displacement 50/60 Hz (1450/1740 ¹/min) | 180,0 / 216,0 m³/h |
Voltage 1) | 380-420V Y/YY -3- 50Hz PW |
| 440-480V Y/YY -3- 60Hz PW |
Winding divided into | 50% / 50% |
Max. working current 2) | 85.1 A |
Max. power consumption 2) | 50.7 kW |
Starting current (rotor blocked) 2) | 196.0 / 335.0 A |
Motor protection | INT69 G |
Protection terminal box | IP 66 |
Weight | 276 kg |
Frequency range 3) | 25 - 60 Hz |
Max. permissible overpressure (g) (LP/HP) 4) | 19 / 32 bar |
Connection suction line SV | 64 mm - 2 5/8 " |
Connection discharge line DV | 42 mm - 1 5/8 " |
Lubrication | Oil pump |
Oil type R290, R1270 | BOCKlub G68 |
Oil charge | 4,4 Ltr. |
Oil sump heater | 230 V - 1 - 50/60 Hz, 160 W |
Dimensions
Length / Width / Height | 810 / 557 / 467 mm |
Sound power level LWA 5) | 89 db(A) @ -35/+40 °C |
| 86 db(A) @ -10/+45 °C |
Sound pressure level LpA 5) | 75 db(A) @ -35/+40 °C |
| 72 db(A) @ -10/+45 °C |
Scope of supply
Semi-hermetic six-cylinder reciprocating compressor with
drive motor for part winding start
Single-section compressor housing with
hermetically integrated electric motor
Rear bearing flange prepared for oil differential pressure
sensor DELTA-P II
Oil pump
Possibility of
connection of oil level controllers ESK, AC+R or CARLY
Winding protection with PTC resistor sensors. Electronic
triggering unit INT69 G to be fitted in switch cupboard (enclosed)
Possibility of connection of oil level controllers Traxoil 6)
Oil charge:
HG HC: BOCKlub G68
Sight glass
Internal safety valve
Suction and discharge line valve
Inert gas charge
Accessories
Start unloader by means of a ESS (Electronic Soft
Start), 400 V - 3 - 50/60 Hz, IP20 (Connection clamps IP00) for installation in
switch cabinet 7)
Capacity regulator 230 V - 1 - 50/60 Hz, IP65
1-2
capacity regulator = 66/33% residual capacity 8)
Cylinder cover prepared for capacity regulator
9)
Oil sump heater 230 V - 1 - 50/60 Hz, 160
W 9)
Oil service valve
Oil pressure safety switch MP54 230 V - 1 - 50/60 Hz,
IP20 7)
Thermal protection thermostat per cylinder cover
9)
Oil differential pressure sensor DELTA-P II 220-240 V -
1 - 50/60 Hz 7)
Connection piece suction and discharge valve in welding
design
INT69 GTML Diagnose 115-230 V AC, 50/60 Hz, IP00,
including oil differential pressure sensor INT250G,
thermal protection
thermostat per cylinder covers, (INT69 G not applicable) 7)
Hot gas temperature sensor (Pt1000, for external
evaluation) 9)
Oil temperature sensor (Pt1000, for external evaluation)
9)
Thermal protection thermostat per cylinder cover
INT69 G Diagnose 115-230 V AC, 50/60 Hz, IP00 (INT69 G
not applicable) 9)
Additional fan
230 V AC - 1 - 50 Hz, 97 W,
IP44
230 V AC - 1 - 60 Hz, 128 W 7)
Step protection 7)
Injection nozzle for liquid injection 7)
4 anti-vibration pads enclosed
Special voltage and/or frequency (on request)
Notes
1) | Tolerance (± 10%)
relates to the mean value of the voltage range. Other voltages and current types
on request
All data are based on voltage rms values
PW = part
winding, motors for part winding starting (no start unloaders required)
Designs for Y/D on request |
2) | - The stated value for the max. power consumption is valid
for the adjusted power supply.
- Starting current (rotor blocked):
- Part winding (PW) motors: Winding 1 / Winding 1+2
- Delta/Star (Δ/Y) motors: Δ / Y
- Take account of the max.
operating current / max. power consumption for designing motor contractors, feed
lines, fuses and motor protection switches. Motor contractors: Consumption
category AC3. |
3) | The maximum permissible working current of the compressor
(Imax) must not be exceeded. Take account of the guidelines for use of frequency
inverter (see compressor assembly instruction or selection software).
|
4) | LP = Low
pressure HP = High pressure |
5) | Declared dual-number noise emission values are in
accordance with ISO 4871. The corresponding uncertainty to the sound power level
is KWA = 2,5 dB and to the sound pressure level is KpA =
2,5 dB. The values are valid for 50 Hz with the refrigerant R404A at the
standard rating points according to EN 12900.
- A-weighted sound power level LWA (re 1 pW), in decibel. To
determine the values, measurement methods of the ISO 3740 standard with
accuracy class 2 or higher were used .
- A-weighted sound pressure level LpA (re 20 µPa), in decibel.
The values are calculated from the sound power level in accordance with ISO
11203: LpA = LWA - Q2 at a distance of d = 1m
to the reference box.
|
6) | Only with additional
adapter possible |
7) | Enclosure |
8) | Capacity regulator premounted, control unit enclosed
|
9) | Mounted |