Technical data
EX-HG88e/2735-4 3G HC
| Application | Refrigeration & AC |
| Compressor refrigeration capacity | 105.00 kW |
| Power consumption | 40.70 kW |
| Current draw (400 V) | 75.90 A |
| Mass flow | 0.356 kg/s |
at following operating condition:
| Refrigerant | R290 |
| Reference temperature | Dew point |
| Evaporating temperature | -10.0 °C |
| Condensing temperature | 45.0 °C |
| Supply frequency | 50 Hz |
| Voltage | 400 V |
| Suction gas temperature | 20 °C |
| Subcooling (outside cond.) | 0 K |
| Number of cylinders / Bore / Stroke | 8 / 80 mm / 68 mm |
| Displacement 50/60 Hz (1450/1740 ¹/min) | 237,90 / 285,50 m³/h |
| Voltage 1) | 380-420V Y/YY -3- 50Hz PW |
| 440-480V Y/YY -3- 60Hz PW |
| Winding divided into | 50% / 50% |
| Max. working current 2) | 116.0 A |
| Max. power consumption 2) | 67.1 kW |
| Starting current (rotor blocked) 2) | 433.0 / 610.0 A |
| Motor protection | INT69 EX2 |
| Protection terminal box | IP 65 |
| Weight | 463 kg |
| Frequency range 3) | 25 - 60 Hz |
| Max. permissible overpressure (g) (LP/HP) 4) | 19 / 28 bar |
| Connection suction line SV | 76 mm - 3 1/8 " |
| Connection discharge line DV | 54 mm - 2 1/8 " |
| Lubrication | Oil pump |
| Oil type R290, R1270 | BOCKlub G68 |
| Oil type R600a | Bock 1516-100 |
| Oil charge | 9,6 Ltr. |
| Oil sump heater | 230 V - 1 - 50/60 Hz, 240 W |
| Dimensions
Length / Width / Height | 943 / 648 / 656 mm |
| Sound power level LWA 5) | 89 dB(A) @ -35 °C / +40 °C |
| 86 dB(A) @ -10 °C / +45 °C |
| Sound pressure level LpA 5) | 75 dB(A) @ -35 °C / +40 °C |
| 72 dB(A) @ -10 °C / +45 °C |
Scope of supply
Semi-hermetic eight-cylinder reciprocating compressor with
drive motor
Single-section Compressor housing with hermetically integrated
electric motor
Oil pump
Possibility of
connection of oil level controllers ESK, AC+R or CARLY 6)
Winding protection with PTC resistor sensors. Electronic
triggering unit to be fitted in switch cupboard (enclosed)
Oil pump cover with screw-in option for oil differential
pressure sensor INT250 EX 6)
Possibility of connection of oil level controllers Traxoil 7)
Oil charge:
HG HC: BOCKlub G68
Three sight glasses
Pressure relief valve
Suction and discharge line valve
Inert gas charge
Accessories
Capacity regulator 230 V - 1 - 50/60 Hz, IP66
1-3
capacity regulator = 75/50/25% residual capacity,
explosion-proof, equipment
category 3 as per directive 2014/34/EU 8)
Cylinder cover prepared for capacity regulator
8)
Oil sump heater 230 V - 1 - 50/60 Hz, 240
W,
explosion-proof, equipment category 3 as per directive 2014/34/EU
8)
Oil service valve 8)
Thermal protection thermostat per cylinder cover
8)
Oil differential pressure sensor INT250
Ex,
explosion-proof, equipment category 3 as per directive 2014/34/EU
8)
Special painting Offshore (Compressor with insulating
coating) incl. Offshore terminal box
Special voltage and/or frequency (on request)
No further
accessories possible
Notes
| 1) | Tolerance (± 10%)
relates to the mean value of the voltage range. Other voltages and current types
on request
All data are based on voltage rms values
PW = part
winding, motors for part winding starting (no start unloaders
required) |
| 2) | - The stated value for the max. power consumption is valid
for the adjusted power supply.
- Starting current (rotor blocked):
- Part winding (PW) motors: Winding 1 / Winding 1+2
- Delta/Star (Δ/Y) motors: Δ / Y
- Take account of the max.
operating current / max. power consumption for designing motor contractors, feed
lines, fuses and motor protection switches. Motor contractors: Consumption
category AC3. |
| 3) | The maximum permissible working current of the compressor
(Imax) must not be exceeded. Take account of the guidelines for use of frequency
inverter (see compressor assembly instruction or selection software).
|
| 4) | LP = Low
pressure HP = High pressure |
| 5) | Declared dual-number noise emission values are in
accordance with ISO 4871. The corresponding uncertainty to the sound power level
is KWA = 2,5 dB and to the sound pressure level is KpA =
2,5 dB. The values are valid for 50 Hz with the refrigerant R404A at the
standard rating points according to EN 12900.
- A-weighted sound power level LWA (re 1 pW), in decibel. To
determine the values, measurement methods of the ISO 3740 standard with
accuracy class 2 or higher were used .
- A-weighted sound pressure level LpA (re 20 µPa), in decibel.
The values are calculated from the sound power level in accordance with ISO
11203: LpA = LWA - Q2 at a distance of d = 1m
to the reference box.
|
| 6) | The operation of this components is only allowed with a
suitable protection class |
| 7) | The operation of this components is only allowed with a
suitable protection class. Only with additional adapter possible.
|
| 8) | Mounted |