Technical data
HGX56/680-4 SH CO2 T
Application | Refrigeration & AC |
Compressor refrigeration capacity | 133.00 kW |
Power consumption | 68.20 kW |
Current draw (400 V) | 119.00 A |
Mass flow | 0.880 kg/s |
at following operating condition:
Refrigerant | R744 |
Reference temperature | Dew point |
Evaporating temperature | -10.0 °C |
High pressure (abs.) | 90.00 bar |
Gas cooler outlet temperature | 35.0 °C |
Supply frequency | 50 Hz |
Voltage | 400 V |
Suction gas superheat | 10 K |
Subcooling (outside cond.) | -- K |
Number of cylinders / Bore / Stroke | 6 / 56 mm / 46 mm |
Displacement 50/60 Hz (1450/1740 ¹/min) | 59,10 / 71,00 m³/h |
Voltage 1) | 380-420V Y/YY -3- 50Hz PW |
| 440-480V Y/YY -3- 60Hz PW |
Winding divided into | 50% / 50% |
Max. working current 2) | 176.0 A |
Max. power consumption 2) | 106.0 kW |
Starting current (rotor blocked) 2) | 592.0 / 834.0 A |
Motor protection | INT69 G |
Protection terminal box | IP 65 |
Weight | 500 kg |
Frequency range 3) | 20 - 70 Hz |
Max. permissible overpressure (g) (LP/HP) 4) | 100 / 150 bar |
Connection suction line SV | 42 mm - 1 5/8 " |
Connection discharge line DV | 35 mm - 1 3/8 " |
Lubrication | Oil pump |
Oil type R744 | Bock C 170 E |
Oil charge | 5.2 Ltr. |
Dimensions
Length / Width / Height | 955 / 562 / 575 mm |
Scope of supply
Semi-hermetic six-cylinder reciprocating compressor with drive motor
Single-section compressor housing with hermetically integrated electric motor
Winding protection with PTC resistor sensors and
electronic trigger unit INT69 G
115-230 V AC, 50/60 Hz,
IP00
Oil pump
Pressure relief valve suction and discharge line
Oil sump heater 230 V - 1 - 50/60 Hz, 220 W
Oil charge:
BOCK C 170 E
Sight glass
Suction and discharge connection using blind flange
Inert gas charge
Accessories
Compressor oil BOCKlub E85 as 1 liter refill
unit 5)
Compressor oil PAG (factory filling) 6)
Oil service valve 7)
Thermal protection thermostat per cylinder cover
Oil differential pressure sensor DELTA-P II 220-240 V - 1
- 50/60 Hz,
incl. oil pump prepared for oil differential pressure sensor
7)
Hot gas temperature sensor (Pt1000, for external
evaluation) 7)
Oil temperature sensor (Pt1000, for external evaluation)
7)
Suction and discharge line valve in soldering / welding
design
INT69 G Diagnose 115-230 V AC, 50/60 Hz, IP00 (INT69 G
not applicable)
Oil level regulator Danfoss COM20C - 230 V AC 50 Hz, PS (MWP) 130 bar, MOPD 80 bar (100 bar) 8)
4 anti-vibration pads enclosed
Special voltage and/or frequency (on request)
Notes
1) | Tolerance (± 10%)
relates to the mean value of the voltage range. Other voltages and current types
on request
All data are based on voltage rms values |
2) | - The stated value for the max. power consumption is valid
for the adjusted power supply.
- Starting current (rotor blocked):
- Part winding (PW) motors: Winding 1 / Winding 1+2
- Delta/Star (Δ/Y) motors: Δ / Y
- Take account of the max.
operating current / max. power consumption for designing motor contractors, feed
lines, fuses and motor protection switches. Motor contractors: Consumption
category AC3. |
3) | The maximum permissible working current of the compressor
(Imax) must not be exceeded. Take account of the guidelines for use of frequency
inverter (see compressor assembly instruction or selection software).
|
4) | LP = Low
pressure HP = High pressure |
5) | Enclosure |
6) | On request |
7) | Mounted |
8) | electrically wired in the terminal box (standard) without cable (option) |