Technical data
HGX46/345-4 ML CO2 T
Application | Refrigeration & AC |
Compressor refrigeration capacity | 67.30 kW |
Power consumption | 35.50 kW |
Current draw (400 V) | 61.60 A |
Mass flow | 0.448 kg/s |
at following operating condition:
Refrigerant | R744 |
Reference temperature | Dew point |
Evaporating temperature | -10.0 °C |
High pressure (abs.) | 90.00 bar |
Gas cooler outlet temperature | 35.0 °C |
Supply frequency | 50 Hz |
Voltage | 400 V |
Suction gas superheat | 10 K |
Subcooling (outside cond.) | -- K |
Number of cylinders / Bore / Stroke | 6 / 40 mm / 46 mm |
Displacement 50/60 Hz (1450/1740 ¹/min) | 30,20 / 36,20 m³/h |
Voltage 1) | 380-420V Y/YY -3- 50Hz PW |
| 440-480V Y/YY -3- 60Hz PW |
Winding divided into | 50% / 50% |
Max. working current 2) | 74.4 A |
Max. power consumption 2) | 44.0 kW |
Starting current (rotor blocked) 2) | 196.0 / 335.0 A |
Motor protection | INT69 G |
Protection terminal box | IP 65 |
Weight | 240 kg |
Frequency range 3) | 20 - 70 Hz |
Max. permissible overpressure (g) (LP/HP) 4) | 100 / 150 bar |
Connection suction line SV | 35 mm - 1 3/8 " |
Connection discharge line DV | 28 mm - 1 1/8 " |
Lubrication | Oil pump |
Oil type R744 | BOCKlub E85 |
Oil charge | 2,6 Ltr. |
Dimensions
Length / Width / Height | 774 / 466 / 403 mm |
Sound power level LWA 5) | 86 dB(A) @ -10 °C / 15 °C / 10 K |
| 84 dB(A) @ -10 °C / 90 bar / 10 K |
Sound pressure level LpA 5) | 73 dB(A) @ -10 °C / 15 °C / 10 K |
| 70 dB(A) @ -10 °C / 90 bar / 10 K |
Scope of supply
Semi-hermetic six-cylinder reciprocating compressor with drive motor
Single-section compressor housing with hermetically integrated electric motor
Winding protection with PTC resistor sensors and
electronic trigger unit INT69 G
115-230 V AC, 50/60 Hz,
IP00
Oil pump
Pressure relief valve suction and discharge line
Oil sump heater 230 V - 1 - 50/60 Hz, 160 W
Oil charge:
BOCKlub E85
Sight glass
Inert gas charge
Suction and pressure connection using blind flange
Accessories
Compressor oil BOCKlub E85 as 1 liter refill
unit 6)
Compressor oil PAG (factory filling) 7)
Digital power controller DCR22 CO2
flexxCO2NTROL
220-240 V -1- 50/60 Hz, 8W, IP65
incl. thermal
protection thermostat (PTC) on cylinder bench with DCR22 CO2
for
further information see 96590-DGbF
Hot gas temperature sensor (Pt1000, for external
evaluation)
recommended for DCR22 CO2
flexxCO2NTROL
for further information see 96590-DGbF
Oil temperature sensor (Pt1000, for external evaluation)
Oil differential pressure sensor DELTA-P II 220-240 V - 1
- 50/60 Hz,
incl. oil pump prepared for oil differential pressure sensor
6)
Thermal protection thermostat per cylinder cover
Suction and discharge line valve in soldering / welding
design
Suction and discharge line valve with cutting ring
connection for steel pipes
Intermediate adapter for discharge line valve 6)
Screw adapter for oil level regulator 6)
4 anti-vibration pads enclosed
Special voltage and/or frequency (on request)
Notes
1) | Tolerance (± 10%)
relates to the mean value of the voltage range. Other voltages and current types
on request
All data are based on voltage rms values |
2) | - The stated value for the max. power consumption is valid
for the adjusted power supply.
- Starting current (rotor blocked):
- Part winding (PW) motors: Winding 1 / Winding 1+2
- Delta/Star (Δ/Y) motors: Δ / Y
- Take account of the max.
operating current / max. power consumption for designing motor contractors, feed
lines, fuses and motor protection switches. Motor contractors: Consumption
category AC3. |
3) | The maximum permissible working current of the compressor
(Imax) must not be exceeded. Take account of the guidelines for use of frequency
inverter (see compressor assembly instruction or selection software).
|
4) | LP = Low
pressure HP = High pressure |
5) | Declared dual-number noise emission values are in
accordance with ISO 4871. The corresponding uncertainty to the sound power level
is KWA = 2,5 dB and to the sound pressure level is KpA =
2,5 dB. The values are valid for 50 Hz with the refrigerant R744 at the standard
rating points according to EN 12900.
- A-weighted sound power level LWA (re 1 pW), in decibel. To
determine the values, measurement methods of the ISO 3740 standard with
accuracy class 2 or higher were used.
- A-weighted sound pressure level LpA (re 20 µPa), in decibel.
The values are calculated from the sound power level in accordance with ISO
11203: LpA = LWA - Q2 at a distance of d = 1m
to the reference box.
|
6) | Enclosure |
7) | On request |