Technical data
HGX24/90-4 S CO2 T
| Application | Refrigeration & AC |
| Compressor refrigeration capacity | 15.80 kW |
| Power consumption | 8.98 kW |
| Current draw (400 V) | 15.50 A |
| Mass flow | 0.105 kg/s |
at following operating condition:
| Refrigerant | R744 |
| Reference temperature | Dew point |
| Evaporating temperature | -10.0 °C |
| High pressure (abs.) | 90.00 bar |
| Gas cooler outlet temperature | 35.0 °C |
| Supply frequency | 50 Hz |
| Voltage | 400 V |
| Suction gas superheat | 10 K |
| Subcooling (outside cond.) | -- K |
| Number of cylinders / Bore / Stroke | 4 / 36 mm / 21,5 mm |
| Displacement 50/60 Hz (1450/1740 ¹/min) | 7,60 / 9,10 m³/h |
| Voltage 1) | 220-240V Δ / 380-420V Y -3- 50Hz |
| 265-290V Δ / 440-480V Y -3- 60Hz |
| Max. working current 2) | 38.4 / 22.2 A |
| Max. power consumption 2) | 13.5 kW |
| Starting current (rotor blocked) 2) | 169.0 / 98.0 A |
| Motor protection | INT69 G |
| Protection terminal box | IP 66 |
| Weight | 116 kg |
| Frequency range 3) | 30 -70 Hz |
| Max. permissible overpressure (g) (LP/HP) 4) | 100 / 150 bar |
| Connection suction line SV | 22 mm - 7/8 " |
| Connection discharge line DV | 19 mm - 3/4 " |
| Lubrication | Oil pump |
| Oil type R744 | BOCKlub E85 |
| Oil charge | 1,5 Ltr. |
| Dimensions
Length / Width / Height | 546 / 351 / 344 mm |
| Sound power level LWA 5) | 74 db(A) @ -10 °C / 15 °C / 10 K |
| 74 db(A) @ -10 °C / 90 bar / 10 K |
| Sound pressure level LpA 5) | 61 db(A) @ -10 °C / 15 °C / 10 K |
| 61 db(A) @ -10 °C / 90 bar / 10 K |
Scope of supply
Semi-hermetic
four-cylinder reciprocating compressor with drive motor - 4-pole design
Single-part compressor housing
Winding protection with PTC resistor sensors and
electronic trigger unit INT69 G
115-230 V AC, 50/60 Hz,
IP00
Oil pump
Oil sump heater 230 V - 1 - 50/60 Hz, 80 W
Oil charge:
BOCKlub E85
Sight glass
Decompression valve HP
Suction and discharge connection using blind flange
Inert gas charge
Notes
| 1) | Tolerance (± 10%)
relates to the mean value of the voltage range. Other voltages and current types
on request
All data are based on voltage rms values |
| 2) | - The stated value for the max. power consumption is valid
for the adjusted power supply.
- Starting current (rotor blocked):
- Part winding (PW) motors: Winding 1 / Winding 1+2
- Delta/Star (Δ/Y) motors: Δ / Y
- Take account of the max.
operating current / max. power consumption for designing motor contractors, feed
lines, fuses and motor protection switches. Motor contractors: Consumption
category AC3. |
| 3) | The maximum permissible working current of the compressor
(Imax) must not be exceeded. Take account of the guidelines for use of frequency
inverter (see compressor assembly instruction or selection software).
|
| 4) | LP = Low
pressure HP = High pressure |
| 5) | Declared dual-number noise emission values are in
accordance with ISO 4871. The corresponding uncertainty to the sound power level
is KWA = 2,5 dB and to the sound pressure level is KpA =
2,5 dB. The values are valid for 50 Hz with the refrigerant R744 at the standard
rating points according to EN 12900.
- A-weighted sound power level LWA (re 1 pW), in decibel. To
determine the values, measurement methods of the ISO 3740 standard with
accuracy class 2 or higher were used.
- A-weighted sound pressure level LpA (re 20 µPa), in decibel.
The values are calculated from the sound power level in accordance with ISO
11203: LpA = LWA - Q2 at a distance of d = 1m
to the reference box.
|