Technical data
HGX12/30-4 ML CO2 T
Application | Refrigeration & AC |
Compressor refrigeration capacity | 5.21 kW |
Power consumption | 3.23 kW |
Current draw (400 V) | 7.41 A |
Mass flow | 0.035 kg/s |
at following operating condition:
Refrigerant | R744 |
Reference temperature | Dew point |
Evaporating temperature | -10.0 °C |
High pressure (abs.) | 90.00 bar |
Gas cooler outlet temperature | 35.0 °C |
Supply frequency | 50 Hz |
Voltage | 400 V |
Suction gas superheat | 10 K |
Subcooling (outside cond.) | -- K |
Number of cylinders / Bore / Stroke | 2 / 36 mm / 16 mm |
Displacement 50/60 Hz (1450/1740 ¹/min) | 2,80 / 3,40 m³/h |
Voltage | 220-240V Δ / 380-420V Y -3- 50Hz |
| 265-290V Δ / 440-480V Y -3- 60Hz |
Max. working current 1) | 14.2 / 8.2 A |
Max. power consumption 1) | 4.0 kW |
Starting current (rotor blocked) 1) | 111.0 / 64.0 A |
Motor protection | INT69 G |
Protection terminal box | IP 66 |
Weight | 95 kg |
Frequency range 2) | 30 -70 Hz |
Max. permissible overpressure (g) (LP/HP) 3) | 100 / 150 bar |
Connection suction line SV | 22 mm - 7/8 " |
Connection discharge line DV | 19 mm - 3/4 " |
Lubrication | Oil pump |
Oil type R744 | BOCKlub E85 |
Oil charge | 1,3 Ltr. |
Dimensions
Length / Width / Height | 503 / 293 / 338 mm |
Sound pressure level LpA | < 70 dB(A) |
Scope of supply
Semi-hermetic two cylinder reciprocating compressor with
drive motor
Single-section compressor housing with hermetically integrated
electric motor
Winding protection with PTC resistor sensors and
electronic trigger unit INT69 G
115-230 V AC, 50/60 Hz,
IP00
Oil pump
Pressure relief valve suction and discharge line
Oil sump heater 230 V - 1 - 50/60 Hz, 80 W
Oil charge:
BOCKlub E85
Sight glass
Suction and discharge connection using blind flange
Inert gas charge
Accessories
Compressor oil BOCKlub E85 as 1 liter refill
unit 4)
Compressor oil PAG (factory filling) 5)
Oil sump heater 24 V
DC, 80 W
Steel terminal box
Thermal protection thermostat
Discharge shut-off valve with cutting ring connection for
steel pipes 6)
Hot gas temperature sensor (Pt1000, for external
evaluation)
Oil temperature sensor (Pt1000, for external evaluation)
Suction and discharge line valve in soldering / welding
design
Oil level regulator Danfoss COM20C - 230 V AC 50 Hz, PS (MWP) 130 bar, MOPD 80 bar (100 bar) 7)
4 anti-vibration pads enclosed 4)
Special voltage and/or frequency (on request)
Notes
1) | - The stated value for the max. power consumption is valid
for the adjusted power supply.
- Starting current (rotor blocked):
- Part winding (PW) motors: Winding 1 / Winding 1+2
- Delta/Star (Δ/Y) motors: Δ / Y
- Take account of the max.
operating current / max. power consumption for designing motor contractors, feed
lines, fuses and motor protection switches. Motor contractors: Consumption
category AC3. |
2) | The maximum permissible working current of the compressor
(Imax) must not be exceeded. Take account of the guidelines for use of frequency
inverter (see compressor assembly instruction or selection software).
|
3) | LP = Low
pressure HP = High pressure |
4) | Enclosure |
5) | On request |
6) | Ø 18 mm |
7) | electrically wired in the terminal box (standard) without cable (option) |