Technical data
HGX34e/170-4 S CO2
Application | Refrigeration & AC |
Compressor refrigeration capacity | 26.40 kW |
Power consumption | 6.25 kW |
Current draw (400 V) | 12.00 A |
Mass flow | 0.102 kg/s |
at following operating condition:
Refrigerant | R744 |
Reference temperature | Dew point |
Evaporating temperature | -35.0 °C |
Condensing temperature | -5.0 °C |
Supply frequency | 50 Hz |
Voltage | 400 V |
Suction gas superheat | 10 K |
Subcooling (outside cond.) | 0 K |
Number of cylinders / Bore / Stroke | 4 / 45 mm / 27 mm |
Displacement 50/60 Hz (1450/1740 ¹/min) | 14,90 / 17,90 m³/h |
Voltage 1) | 220-240V Δ / 380-420V Y -3- 50Hz |
| 265-290V Δ / 440-480V Y -3- 60Hz |
Max. working current 2) | 30.1 / 17.4 A |
Max. power consumption 2) | 10.3 kW |
Starting current (rotor blocked) 2) | 169.0 / 98.0 A |
Motor protection | INT69 G |
Protection terminal box | IP 66 |
Weight | 103 kg |
Frequency range 3) | 25 - 70 Hz |
Max. permissible overpressure (g) (LP/HP) 4) | 40 / 55 bar |
Connection suction line SV | 28 mm - 1 1/8 " |
Connection discharge line DV | 22 mm - 7/8 " |
Lubrication | Oil pump |
Oil type R744 | BOCKlub E85 |
Oil charge | 1,3 Ltr. |
Dimensions
Length / Width / Height | 572 / 322 / 318 mm |
Sound power level LWA 5) | 71 db(A) @ -35 °C / -5 °C / 10 K |
| 74 db(A) @ -35 °C / 15 °C / 10 K |
Sound pressure level LpA 5) | 58 db(A) @ -35 °C / -5 °C / 10 K |
| 61 db(A) @ -35 °C / 15 °C / 10 K |
Scope of supply
Semi-hermetic four
cylinder reciprocating compressor with drive motor
Single-section compressor housing with hermetically integrated electric
motor
Winding protection with PTC resistor sensors and
electronic trigger unit INT69 G
115-230 V AC, 50/60 Hz,
IP00
Oil pump
Pressure relief valve suction and discharge line
Possibility of
connection of oil level controllers ESK, Traxoil, AC+R or CARLY 6)
Oil charge:
BOCKlub E85
Sight glass
Suction and discharge line valve in soldering / welding
design
Inert gas charge
Accessories
Compressor oil BOCKlub E85 as 1 liter refill
unit 7)
Oil sump heater
110-240 V - 1 - 50/60 Hz, 50-120 W, IP66
PTC heater
self-regulating
USB converter for INT69 G Diagnose 7)
Thermal protection thermostat per cylinder cover
INT69 G Diagnose 115-230 V AC, 50/60 Hz, IP00 (INT69 G
not applicable)
DP-Modbus Gateway 115-230 V AC, 50/60 Hz, IP00 including
adapter cable 7)
Modbus-LAN Gateway 230 V AC, 50/60 Hz,
IP00 7)
Adapter for pressure relief valve 7)
Additional fan
230 V AC - 1 - 50 Hz, 97 W,
IP44
230 V AC - 1 - 60 Hz, 128 W 7)
Oil level regulator Danfoss COM20C - 230 V AC 50 Hz, PS (MWP) 130 bar, MOPD 80 bar (100 bar) 8)
4 anti-vibration pads enclosed
Special voltage and/or frequency (on request)
Notes
1) | Tolerance (± 10%)
relates to the mean value of the voltage range. Other voltages and current types
on request
All data are based on voltage rms values |
2) | - The stated value for the max. power consumption is valid
for the adjusted power supply.
- Starting current (rotor blocked):
- Part winding (PW) motors: Winding 1 / Winding 1+2
- Delta/Star (Δ/Y) motors: Δ / Y
- Take account of the max.
operating current / max. power consumption for designing motor contractors, feed
lines, fuses and motor protection switches. Motor contractors: Consumption
category AC3. |
3) | The maximum permissible working current of the compressor
(Imax) must not be exceeded. Take account of the guidelines for use of frequency
inverter (see compressor assembly instruction or selection software).
|
4) | LP = Low
pressure HP = High pressure |
5) | Declared dual-number noise emission values are in
accordance with ISO 4871. The corresponding uncertainty to the sound power level
is KWA = 2,5 dB and to the sound pressure level is KpA =
2,5 dB. The values are valid for 50 Hz with the refrigerant R744 at the standard
rating points according to EN 12900.
- A-weighted sound power level LWA (re 1 pW), in decibel. To
determine the values, measurement methods of the ISO 3740 standard with
accuracy class 2 or higher were used.
- A-weighted sound pressure level LpA (re 20 µPa), in decibel.
The values are calculated from the sound power level in accordance with ISO
11203: LpA = LWA - Q2 at a distance of d = 1m
to the reference box.
|
6) | Only with additional
adapter possible |
7) | Enclosure |
8) | electrically wired in the terminal box (standard) without cable (option) |