Technical data
HGX12e/75-4 S CO2
| Application | Refrigeration & AC |
| Compressor refrigeration capacity | 11.10 kW |
| Power consumption | 2.86 kW |
| Current draw (400 V) | 5.95 A |
| Mass flow | 0.043 kg/s |
at following operating condition:
| Refrigerant | R744 |
| Reference temperature | Dew point |
| Evaporating temperature | -35.0 °C |
| Condensing temperature | -5.0 °C |
| Supply frequency | 50 Hz |
| Voltage | 400 V |
| Suction gas superheat | 10 K |
| Subcooling (outside cond.) | 0 K |
| Number of cylinders / Bore / Stroke | 2 / 45 mm / 23 mm |
| Displacement 50/60 Hz (1450/1740 ¹/min) | 6,40 / 7,70 m³/h |
| Voltage 1) | 220-240V Δ / 380-420V Y -3- 50Hz |
| 265-290V Δ / 440-480V Y -3- 60Hz |
| Max. working current 2) | 14.3 / 8.2 A |
| Max. power consumption 2) | 4.7 kW |
| Starting current (rotor blocked) 2) | 71.0 / 41.0 A |
| Motor protection | INT69 G |
| Protection terminal box | IP 66 |
| Weight | 54 kg |
| Frequency range 3) | 30 -70 Hz |
| Max. permissible overpressure (g) (LP/HP) 4) | 40 / 55 bar |
| Connection suction line SV | 16 mm - 5/8 " |
| Connection discharge line DV | 12 mm - 1/2 " |
| Lubrication | Oil pump |
| Oil type R744 | BOCKlub E85 |
| Oil charge | 0,8 Ltr. |
| Dimensions
Length / Width / Height | 441 / 233 / 294 mm |
| Sound power level LWA 5) | 70 db(A) @ -35 °C / -5 °C / 10 K |
| 72 db(A) @ -35 °C / 15 °C / 10 K |
| Sound pressure level LpA 5) | 57 db(A) @ -35 °C / -5 °C / 10 K |
| 60 db(A) @ -35 °C / 15 °C / 10 K |
Scope of supply
Semi-hermetic two cylinder reciprocating compressor with
drive motor
Single-section compressor housing with hermetically integrated
electric motor
Winding protection with PTC resistor sensors and
electronic trigger unit INT69 G
115-230 V AC, 50/60 Hz,
IP00
Oil pump
Pressure relief valve suction and discharge line
Possibility of
connection of oil level controllers ESK, Traxoil, AC+R or CARLY 6)
Oil charge:
BOCKlub E85
Sight glass
Suction and discharge line valve in soldering / welding
design
Inert gas charge
Accessories
Compressor oil BOCKlub E85 as 1 liter refill
unit 7)
Oil sump heater
110-240 V - 1 - 50/60 Hz, 50-120 W, IP66
PTC heater
self-regulating 8)
Thermal protection thermostat
INT69 B2 Diagnose 24 V AC, 50/60 Hz, IP00 (INT69 G not applicable)
Additional fan
230 V AC - 1 - 50 Hz, 72 W, IP44
230 V AC - 1 - 60
Hz, 68 W
7)Adapter for pressure relief valve 7)
Oil level regulator Danfoss COM20C - 24 V AC 50 Hz, PS 130 bar/MWP1885 psig 9)
Oil level regulator Danfoss COM20C - 230 V AC 50 Hz, PS 130 bar/MWP1885 psig 9)
4 anti-vibration pads enclosed
Special voltage and/or frequency (on request)
Notes
| 1) | Tolerance (± 10%)
relates to the mean value of the voltage range. Other voltages and current types
on request
All data are based on voltage rms values |
| 2) | - The stated value for the max. power consumption is valid
for the adjusted power supply.
- Starting current (rotor blocked):
- Part winding (PW) motors: Winding 1 / Winding 1+2
- Delta/Star (Δ/Y) motors: Δ / Y
- Take account of the max.
operating current / max. power consumption for designing motor contractors, feed
lines, fuses and motor protection switches. Motor contractors: Consumption
category AC3. |
| 3) | The maximum permissible working current of the compressor
(Imax) must not be exceeded. Take account of the guidelines for use of frequency
inverter (see compressor assembly instruction or selection software).
|
| 4) | LP = Low
pressure HP = High pressure |
| 5) | Declared dual-number noise emission values are in
accordance with ISO 4871. The corresponding uncertainty to the sound power level
is KWA = 2,5 dB and to the sound pressure level is KpA =
2,5 dB. The values are valid for 50 Hz with the refrigerant R744 at the standard
rating points according to EN 12900.
- A-weighted sound power level LWA (re 1 pW), in decibel. To
determine the values, measurement methods of the ISO 3740 standard with
accuracy class 2 or higher were used.
- A-weighted sound pressure level LpA (re 20 µPa), in decibel.
The values are calculated from the sound power level in accordance with ISO
11203: LpA = LWA - Q2 at a distance of d = 1m
to the reference box.
|
| 6) | Only with additional
adapter possible |
| 7) | Enclosure |
| 8) | Mounted |
| 9) | electrically wired in the terminal box (standard) without cable (option) |