Technical data
HGX12e/30-4 S CO2 LT
Application | Refrigeration & AC |
Compressor refrigeration capacity | 4.30 kW |
Power consumption | 1.42 kW |
Current draw (400 V) | 5.93 A |
Mass flow | 0.017 kg/s |
at following operating condition:
Refrigerant | R744 |
Reference temperature | Dew point |
Evaporating temperature | -35.0 °C |
Condensing temperature | -5.0 °C |
Supply frequency | 50 Hz |
Voltage | 400 V |
Suction gas superheat | 10 K |
Subcooling (outside cond.) | 0 K |
Number of cylinders / Bore / Stroke | 2 / 36 mm / 16 mm |
Displacement 50/60 Hz (1450/1740 ¹/min) | 2,80 / 3,40 m³/h |
Voltage | 220-240V Δ / 380-420V Y -3- 50Hz |
| 265-290V Δ / 440-480V Y -3- 60Hz |
Max. working current 1) | 11.7 / 6.7 A |
Max. power consumption 1) | 2.5 kW |
Starting current (rotor blocked) 1) | 111.0 / 64.0 A |
Motor protection | INT69 G |
Protection terminal box | IP 66 |
Weight | 95 kg |
Frequency range 2) | 30 -70 Hz |
Max. permissible overpressure (g) (LP/HP) 3) | 100 / 100 bar |
Connection suction line SV | 16 mm - 5/8 " |
Connection discharge line DV | 12,8 mm - 1/2 " |
Lubrication | Oil pump |
Oil type R744 | BOCKlub E85 |
Oil charge | 1,3 Ltr. |
Dimensions
Length / Width / Height | 503 / 293 / 338 mm |
Sound pressure level LpA | < 70 dB(A) |
Scope of supply
Semi-hermetic two cylinder reciprocating compressor with
drive motor
Single-section compressor housing with hermetically integrated
electric motor
Winding protection with PTC resistor sensors and
electronic trigger unit INT69 G
115-230 V AC, 50/60 Hz,
IP00
Oil pump
Pressure relief valve suction and discharge line
Oil charge:
BOCKlub E85
Sight glass
Suction and discharge line valve in soldering / welding
design
Inert gas charge
Accessories
Compressor oil BOCKlub E85 as 1 liter refill
unit 4)
Oil sump heater 230 V - 1 - 50/60 Hz, 80 W
Steel terminal box
Thermal protection thermostat
Oil temperature sensor (Pt1000, for external evaluation)
Hot gas temperature sensor (Pt1000, for external
evaluation)
Oil level regulator Danfoss COM20C - 230 V AC 50 Hz, PS (MWP) 130 bar, MOPD 80 bar (100 bar) 5)
4 anti-vibration pads enclosed
Special voltage and/or frequency (on request)
Notes
1) | - The stated value for the max. power consumption is valid
for the adjusted power supply.
- Starting current (rotor blocked):
- Part winding (PW) motors: Winding 1 / Winding 1+2
- Delta/Star (Δ/Y) motors: Δ / Y
- Take account of the max.
operating current / max. power consumption for designing motor contractors, feed
lines, fuses and motor protection switches. Motor contractors: Consumption
category AC3. |
2) | The maximum permissible working current of the compressor
(Imax) must not be exceeded. Take account of the guidelines for use of frequency
inverter (see compressor assembly instruction or selection software).
|
3) | LP = Low
pressure HP = High pressure |
4) | Enclosure |
5) | electrically wired in the terminal box (standard) without cable (option) |