Technical data
HGX66e/2070-4
Application | Refrigeration & AC |
Compressor refrigeration capacity | 98.30 kW |
Power consumption | 29.90 kW |
Current draw (400 V) | 53.70 A |
Mass flow | 0.688 kg/s |
at following operating condition:
Refrigerant | R134a |
Reference temperature | Dew point |
Evaporating temperature | 5.0 °C |
Condensing temperature | 50.0 °C |
Supply frequency | 50 Hz |
Voltage | 400 V |
Suction gas temperature | 20 °C |
Subcooling (outside cond.) | 0 K |
Number of cylinders / Bore / Stroke | 6 / 87 mm / 58 mm |
Displacement 50/60 Hz (1450/1740 ¹/min) | 180,0 / 216,0 m³/h |
Voltage 1) | 380-420V Y/YY -3- 50Hz PW |
| 440-480V Y/YY -3- 60Hz PW |
Winding divided into | 50% / 50% |
Max. working current 2) | 85.1 A |
Max. power consumption 2) | 50.7 kW |
Starting current (rotor blocked) 2) | 196.0 / 335.0 A |
Motor protection | INT69 G |
Protection terminal box | IP 66 |
Weight | 276 kg |
Frequency range 3) | 25 - 60 Hz |
Max. permissible overpressure (g) (LP/HP) 4) | 19 / 28 bar |
Connection suction line SV | 64 mm - 2 5/8 " |
Connection discharge line DV | 42 mm - 1 5/8 " |
Lubrication | Oil pump |
Oil type R134a, R404A, R407A/C/F, R448A, R449A, R450A, R513A | BOCKlub E55 |
Oil type R22 | BOCKlub A46 |
Oil charge | 4,4 Ltr. |
Oil sump heater | 230 V - 1 - 50/60 Hz, 160 W |
Dimensions
Length / Width / Height | 810 / 557 / 467 mm |
Sound power level LWA 5) | 89 db(A) @ -35/+40 °C |
| 86 db(A) @ -10/+45 °C |
Sound pressure level LpA 5) | 75 db(A) @ -35/+40 °C |
| 72 db(A) @ -10/+45 °C |
Scope of supply
Semi-hermetic six-cylinder reciprocating compressor with
drive motor for part winding start
Single-section compressor housing with
hermetically integrated electric motor
Rear bearing flange prepared for oil differential pressure
sensor DELTA-P II
Winding protection with PTC resistor sensors and
electronic trigger unit INT69 G
115-230 V AC, 50/60 Hz,
IP00
Oil pump
Possibility of
connection of oil level controllers ESK, AC+R or CARLY
Possibility of connection of oil level controllers Traxoil 6)
Oil charge:
HG: BOCKlub A46
HGX:
BOCKlub E55
Sight glass
Internal safety valve
Suction and discharge line valve
Inert gas charge
Accessories
Capacitiy regulator 110 V - 1 - 50/60 Hz, IP65
1-2
capacity regulator = 66/33% residual capacity 7)
Capacity regulator 230 V - 1 - 50/60 Hz, IP65
1-2
capacity regulator = 66/33% residual capacity 7)
Cylinder cover prepared for capacity regulator
8)
Oil sump heater 230 V - 1 - 50/60 Hz, 160
W 8)
Oil service valve
USB converter for INT69 G Diagnose 9)
Oil pressure safety switch MP54 230 V - 1 - 50/60 Hz,
IP20 9)
Thermal protection thermostat per cylinder cover
8)
Oil differential pressure sensor DELTA-P II 220-240 V -
1 - 50/60 Hz 9)
Connection piece suction and discharge valve in welding
design
INT69 GTML Diagnose 115-230 V AC, 50/60 Hz, IP00,
including oil differential pressure sensor INT250G,
thermal protection
thermostat per cylinder covers, (INT69 G not applicable) 9)
Hot gas temperature sensor (Pt1000, for external
evaluation) 8)
Oil temperature sensor (Pt1000, for external evaluation)
8)
Thermal protection thermostat per cylinder cover
INT69 G Diagnose 115-230 V AC, 50/60 Hz, IP00 (INT69 G
not applicable) 8)
DP-Modbus Gateway 115-230 V AC, 50/60 Hz, IP00 including
adapter cable 9)
Modbus-LAN Gateway 230 V AC, 50/60 Hz,
IP00 9)
Additional fan
230 V AC - 1 - 50 Hz, 97 W,
IP44
230 V AC - 1 - 60 Hz, 128 W 9)
Step protection 9)
Injection nozzle for liquid injection 9)
4 anti-vibration pads enclosed
Special voltage and/or frequency (on request)
Notes
1) | Tolerance (± 10%)
relates to the mean value of the voltage range. Other voltages and current types
on request
All data are based on voltage rms values
PW = part
winding, motors for part winding starting (no start unloaders required)
Designs for Y/D on request |
2) | - The stated value for the max. power consumption is valid
for the adjusted power supply.
- Starting current (rotor blocked):
- Part winding (PW) motors: Winding 1 / Winding 1+2
- Delta/Star (Δ/Y) motors: Δ / Y
- Take account of the max.
operating current / max. power consumption for designing motor contractors, feed
lines, fuses and motor protection switches. Motor contractors: Consumption
category AC3. |
3) | The maximum permissible working current of the compressor
(Imax) must not be exceeded. Take account of the guidelines for use of frequency
inverter (see compressor assembly instruction or selection software).
|
4) | LP = Low
pressure HP = High pressure |
5) | Declared dual-number noise emission values are in
accordance with ISO 4871. The corresponding uncertainty to the sound power level
is KWA = 2,5 dB and to the sound pressure level is KpA =
2,5 dB. The values are valid for 50 Hz with the refrigerant R404A at the
standard rating points according to EN 12900.
- A-weighted sound power level LWA (re 1 pW), in decibel. To
determine the values, measurement methods of the ISO 3740 standard with
accuracy class 2 or higher were used .
- A-weighted sound pressure level LpA (re 20 µPa), in decibel.
The values are calculated from the sound power level in accordance with ISO
11203: LpA = LWA - Q2 at a distance of d = 1m
to the reference box.
|
6) | Only with additional
adapter possible |
7) | Capacity regulator premounted, control unit enclosed
|
8) | Mounted |
9) | Enclosure |