Semi-hermetic, suction gas-cooled 8-cylinder reciprocating compressor in
compact design with optimized valve plate system “mexxFlow”. “mexxflow” is a
highly efficient and reliable valve plate system with higher refrigeration
capacity at lower power consumption. The compressor shows best possible
serviceability (e.g. by means of a replaceable drive motor), outstanding running
comfort and efficient operating performance. The suction cover can be rotated by
90° in each instance. Dependable mechanism lubrication is guaranteed by means of
an oil pump which is independent of rotating direction, as well as a
large-volume oil sump. The optional oil sump heater is using an immersion sleeve
and can therefore be replaced without intervening in the refrigeration cycle. A
direct connection facility for an oil level regulator is possible on one of the
three standard sight glasses. The large-volume electric terminal box in solid
metal design has easy quick-release fasteners. The electronic motor protection
INT69G uses PTC sensors to monitor the winding temperature (as standard
equipment) and optional the discharge gas temperature.
Colour: blue (RAL 5000)
Technical data
HGX88e/2400-4 S
| Application | Refrigeration & AC |
| Compressor refrigeration capacity | 117.00 kW |
| Power consumption | 35.90 kW |
| Current draw (400 V) | 72.60 A |
| Mass flow | 0.814 kg/s |
at following operating condition:
| Refrigerant | R134a |
| Reference temperature | Dew point |
| Evaporating temperature | 5.0 °C |
| Condensing temperature | 50.0 °C |
| Supply frequency | 50 Hz |
| Voltage | 400 V |
| Suction gas temperature | 20 °C |
| Subcooling (outside cond.) | 0 K |
| Number of cylinders / Bore / Stroke | 8 / 75 mm / 68 mm |
| Displacement 50/60 Hz (1450/1740 ¹/min) | 209,1 / 250,9 m³/h |
| Voltage 1) | 380-420V Y/YY -3- 50Hz PW |
| 440-480V Y/YY -3- 60Hz PW |
| Winding divided into | 50% / 50% |
| Max. working current 2) | 120.0 A |
| Max. power consumption 2) | 69.8 kW |
| Starting current (rotor blocked) 2) | 466.0 / 657.0 A |
| Motor protection | INT69 G |
| Protection terminal box | IP 65 |
| Weight | 452 kg |
| Frequency range 3) | 25 - 60 Hz |
| Max. permissible overpressure (g) (LP/HP) 4) | 19 / 28 bar |
| Connection suction line SV | 76 mm - 3 1/8 " |
| Connection discharge line DV | 54 mm - 2 1/8 " |
| Lubrication | Oil pump |
| Oil type R134a, R404A, R407A/C/F, R448A, R449A, R450A, R513A | BOCKlub E55 |
| Oil type R22 | BOCKlub A46 |
| Oil charge | 9,6 Ltr. |
| Oil sump heater | 230 V - 1 - 50/60 Hz, 200 W |
| Dimensions
Length / Width / Height | 943 / 648 / 656 mm |
| Sound power level LWA 5) | 89 dB(A) @ -35 °C / +40 °C |
| 86 dB(A) @ -10 °C / +45 °C |
| 85 dB(A) @ +5 °C / +50 °C |
| Sound pressure level LpA 5) | 76 dB(A) @ -35 °C / +40 °C |
| 72 dB(A) @ -10 °C / +45 °C |
| 71 dB(A) @ +5 °C / +50 °C |
Scope of supply
Semi-hermetic eight-cylinder reciprocating compressor with
drive motor
Single-section Compressor housing with hermetically integrated
electric motor
Winding protection with PTC resistor sensors and
electronic trigger unit INT69 G
115-230 V AC, 50/60 Hz,
IP00
Oil pump
Possibility of
connection of oil level controllers ESK, AC+R or CARLY
Oil pump cover with screw-in option for oil differential
pressure sensor DELTA-P II
Possibility of connection of oil level controllers Traxoil 6)
Possibility for connection of oil pressure safety switch
MP54
Oil charge:
HG: BOCKlub A46
HGX:
BOCKlub E55
Three sight glasses
Pressure relief valve
Suction and discharge line valve
Inert gas charge
Accessories
Capacitiy regulator 110 V - 1 - 50/60 Hz, IP65
1-3
capacity regulator = 75/50/25% residual capacity 7)
Capacity regulator 230 V - 1 - 50/60 Hz, IP65
1-3 capacity regulator = 75/50/25% residual capacity 7)
Cylinder cover prepared for capacity regulator
Oil sump heater 230 V - 1 - 50/60 Hz, 200 W 8)
Oil service valve 8)
INT69 GTML Diagnose 115-230 V AC, 50/60 Hz, IP00,
including oil differential pressure sensor INT250G,
thermal protection
thermostat per cylinder covers, (INT69 G not applicable)
Oil pressure safety switch MP54 230 V - 1 - 50/60 Hz,
IP20 9)
Thermal protection thermostat per cylinder cover
8)
Connection piece suction and discharge valve in welding
design
Oil differential pressure sensor DELTA-P II 220-240 V -
1 - 50/60 Hz 9)
Oil temperature sensor (Pt1000, for external evaluation)
8)
Hot gas temperature sensor (Pt1000, for external
evaluation) 8)
Thermal protection thermostat per cylinder cover
USB converter for INT69 G Diagnose and INT69 GTML
Diagnose 9)
Additional fan
230 V AC - 1 - 50 Hz, 97 W,
IP44
230 V AC - 1 - 60 Hz, 128 W 9)
Intermediate adapter for discharge line valve 9)
Step protection
4 anti-vibration pads enclosed
Special voltage and/or frequency (on request)
Notes
| 1) | Tolerance (± 10%)
relates to the mean value of the voltage range. Other voltages and current types
on request
All data are based on voltage rms values
PW = part
winding, motors for part winding starting (no start unloaders required)
Designs for Y/D on request |
| 2) | - The stated value for the max. power consumption is valid
for the adjusted power supply.
- Starting current (rotor blocked):
- Part winding (PW) motors: Winding 1 / Winding 1+2
- Delta/Star (Δ/Y) motors: Δ / Y
- Take account of the max.
operating current / max. power consumption for designing motor contractors, feed
lines, fuses and motor protection switches. Motor contractors: Consumption
category AC3. |
| 3) | The maximum permissible working current of the compressor
(Imax) must not be exceeded. Take account of the guidelines for use of frequency
inverter (see compressor assembly instruction or selection software).
|
| 4) | LP = Low
pressure HP = High pressure |
| 5) | Declared dual-number noise emission values are in
accordance with ISO 4871. The corresponding uncertainty to the sound power level
is KWA = 2,5 dB and to the sound pressure level is KpA =
2,5 dB. The values are valid for 50 Hz with the refrigerant R404A at the
standard rating points according to EN 12900.
- A-weighted sound power level LWA (re 1 pW), in decibel. To
determine the values, measurement methods of the ISO 3740 standard with
accuracy class 2 or higher were used .
- A-weighted sound pressure level LpA (re 20 µPa), in decibel.
The values are calculated from the sound power level in accordance with ISO
11203: LpA = LWA - Q2 at a distance of d = 1m
to the reference box.
|
| 6) | Only with additional
adapter possible |
| 7) | Capacity regulator premounted, control unit enclosed
|
| 8) | Mounted |
| 9) | Enclosure |