Technical data
HAX22e/190 LT 3 LG
Application | Refrigeration & AC |
Compressor refrigeration capacity | 2.81 kW |
Power consumption | 2.04 kW |
Current draw (400 V) | 4.52 A |
Mass flow | 0.021 kg/s |
at following operating condition:
Refrigerant | R404A, R507 |
Reference temperature | Dew point |
Evaporating temperature | -35.0 °C |
Condensing temperature | 40.0 °C |
Supply frequency | 50 Hz |
Voltage | 400 V |
Suction gas temperature | 20 °C |
Subcooling (outside cond.) | 0 K |
Number of cylinders / Bore / Stroke | 2 / 55 mm / 40 mm |
Displacement 50/60 Hz (1450/1740 ¹/min) | 16,50 / 19,80 m³/h |
Voltage 1) | 220-240V Δ / 380-420V Y -3- 50Hz |
| 265-290V Δ / 440-480V Y -3- 60Hz |
Max. working current 2) | 10.9 / 6.3 A |
Max. power consumption 2) | 3.5 kW |
Starting current (rotor blocked) 2) | 87.0 / 50.0 A |
Motor protection | INT69 G |
Protection terminal box / HA-fan | IP 66 / IP 44 |
Voltage HA-fan | 230 V - 1 - 50/60 Hz, 38 W |
Weight | 76 kg |
Frequency range 3) | 30 -70 Hz |
Max. permissible overpressure (g) (LP/HP) 4) | 19 / 32 bar |
Connection suction line SV | 16 mm - 5/8 " |
Connection discharge line DV | 12 mm - 1/2 " |
Lubrication | Oil pump |
Oil type R134a, R404A, R407A/C/F, R448A, R449A, R450A, R513A | BOCKlub E55 |
Oil type R1234yf, R1234ze, R455A, R454C | BOCKlub E55 |
Oil charge | 1,1 Ltr. |
Dimensions
Length / Width / Height | 524 / 303 / 315 mm |
Scope of supply
Semi-hermetic two cylinder reciprocating compressor with
drive motor
Single-section compressor housing with hermetically integrated
electric motor
Motor is cooled by an integrated ventilator with air
deflection hood.
230 V - 1 - 50/60 Hz, 38 W, 0,17 A
Oil pump
Winding protection with PTC resistor sensors and
electronic triggering unit INT69 G to be fitted in switch cupboard
(enclosed)
115-230 V AC, 50/60 Hz, IP00
Possibility of
connection of oil level controllers ESK, Traxoil, AC+R or CARLY 5)
Oil charge:
BOCKlub E55
Sight glass
Suction and discharge line valve
Inert gas charge
4 anti-vibration pads enclosed
Accessories
Oil sump heater
230 V - 1 - 50/60 Hz, 160 W,
IP66
PTC heater self-regulating
Thermal protection thermostat per cylinder cover
6)
Hot gas temperature sensor (Pt1000, for external
evaluation) 6)
Thermal protection thermostat per cylinder cover
Special voltage and/or frequency (on request)
Notes
1) | Tolerance (± 10%)
relates to the mean value of the voltage range. Other voltages and current types
on request
All data are based on voltage rms values |
2) | - The stated value for the max. power consumption is valid
for the adjusted power supply.
- Starting current (rotor blocked):
- Part winding (PW) motors: Winding 1 / Winding 1+2
- Delta/Star (Δ/Y) motors: Δ / Y
- Take account of the max.
operating current / max. power consumption for designing motor contractors, feed
lines, fuses and motor protection switches. Motor contractors: Consumption
category AC3. |
3) | The maximum permissible working current of the compressor
(Imax) must not be exceeded. Take account of the guidelines for use of frequency
inverter (see compressor assembly instruction or selection software).
|
4) | LP = Low
pressure HP = High pressure |
5) | Only with additional
adapter possible |
6) | Mounted |