Technical data
HAX44e/475-4
Application | Refrigeration & AC |
Compressor refrigeration capacity | 7.43 kW |
Power consumption | 4.62 kW |
Current draw (400 V) | 12.30 A |
Mass flow | 0.056 kg/s |
at following operating condition:
Refrigerant | R404A, R507 |
Reference temperature | Dew point |
Evaporating temperature | -35.0 °C |
Condensing temperature | 40.0 °C |
Supply frequency | 50 Hz |
Voltage | 400 V |
Suction gas temperature | 20 °C |
Subcooling (outside cond.) | 0 K |
Number of cylinders / Bore / Stroke | 4 / 55 mm / 50 mm |
Displacement 50/60 Hz (1450/1740 ¹/min) | 41,30 / 49,60 m³/h |
Voltage 1) | 380-420V Y/YY -3- 50Hz PW |
| 440-480V Y/YY -3- 60Hz PW |
Winding divided into | 50% / 50% |
Max. working current 2) | 15.2 A |
Max. power consumption 2) | 7.6 kW |
Starting current (rotor blocked) 2) | 87.0 / 149.0 A |
Motor protection | INT69 G |
Protection terminal box / HA-fan | IP 66 / IP 44 |
Voltage HA-fan | 230 V - 1 - 50/60 Hz, 140 W |
Protection terminal box | IP 66 |
Weight | 174 kg |
Frequency range 3) | 25 - 70 Hz |
Max. permissible overpressure (g) (LP/HP) 4) | 19 / 28 bar |
Connection suction line SV | 35 mm - 1 3/8 " |
Connection discharge line DV | 28 mm - 1 1/8 " |
Lubrication | Oil pump |
Oil type R134a, R404A, R407A/C/F, R448A, R449A, R450A, R513A | BOCKlub E55 |
Oil type R22 | BOCKlub A46 |
Oil charge | 2,7 Ltr. |
Oil sump heater | 230 V - 1 - 50/60 Hz, 160 W |
Dimensions
Length / Width / Height | 717 / 361 / 408 mm |
Sound power level LWA 5) | 81 db(A) @ -35 °C / +40 °C |
Sound pressure level LpA 5) | 68 dB(A) @ -35 °C / +40 °C |
Scope of supply
Semi-hermetic four-cylinder reciprocating compressor
with drive motor for part winding start
380-420 V Y/YY - 3 - 50 Hz
440-480
V Y/YY - 3 - 60 Hz
Single-section compressor housing with hermetically
integrated electric motor
Motor is cooled by an integrated ventilator with air
deflection hood.
230 V - 1 - 50/60 Hz, IP44, 140 W, 0,71 A
Rear bearing flange prepared for oil differential pressure
sensor DELTA-P II
Winding protection with PTC resistor sensors and
electronic trigger unit INT69 G
115-230 V AC, 50/60 Hz,
IP00
Oil pump
Possibility of
connection of oil level controllers ESK, AC+R or CARLY
Possibility of connection of oil level controllers Traxoil 6)
Possibility for connection of oil pressure safety switch
MP54
Oil charge:
HA: BOCKlub A46
HAX:
BOCKlub E55
Sight glass
Pressure relief valve
Suction and discharge line valve
Inert gas charge
Accessories
Digital capacity regulator DCR14 230 V - 1 - 50/60
Hz, IP65
1 digital capacity regulator = 50% residual capacity 7)
Cylinder cover prepared for digital capacity regulator
Oil sump heater
230 V - 1 - 50/60 Hz, 160 W,
IP66
PTC heater self-regulating
USB converter for INT69 G Diagnose 8)
Oil pressure safety switch MP54 230 V - 1 - 50/60 Hz,
IP20 8)
Oil differential pressure sensor DELTA-P II 220-240 V -
1 - 50/60 Hz 9)
Connection piece suction and discharge valve in welding
design 10)
Thermal protection thermostat per cylinder cover
7)
Oil temperature sensor (Pt1000, for external evaluation)
7)
Hot gas temperature sensor (Pt1000, for external
evaluation) 7)
Thermal protection thermostat per cylinder cover
INT69 G Diagnose 115-230 V AC, 50/60 Hz, IP00 (INT69 G
not applicable)
DP-Modbus Gateway 115-230 V AC, 50/60 Hz, IP00 including
adapter cable 8)
Modbus-LAN Gateway 230 V AC, 50/60 Hz,
IP00 8)
Intermediate flange for suction valve on right
seen from oil pump in conjunction with capacity regulator 8)
Step protection
4 anti-vibration pads enclosed
Special voltage and/or frequency (on request)
Notes
1) | Tolerance (± 10%)
relates to the mean value of the voltage range. Other voltages and current types
on request
All data are based on voltage rms values
PW = part
winding, motors for part winding starting (no start unloaders required)
Designs for Y/D on request |
2) | - The stated value for the max. power consumption is valid
for the adjusted power supply.
- Starting current (rotor blocked):
- Part winding (PW) motors: Winding 1 / Winding 1+2
- Delta/Star (Δ/Y) motors: Δ / Y
- Take account of the max.
operating current / max. power consumption for designing motor contractors, feed
lines, fuses and motor protection switches. Motor contractors: Consumption
category AC3. |
3) | The maximum permissible working current of the compressor
(Imax) must not be exceeded. Take account of the guidelines for use of frequency
inverter (see compressor assembly instruction or selection software).
|
4) | LP = Low
pressure HP = High pressure |
5) | Declared dual-number noise emission values are in
accordance with ISO 4871. The corresponding uncertainty to the sound power level
is KWA = 2,5 dB and to the sound pressure level is KpA =
2,5 dB. The values are valid for 50 Hz with the refrigerant R404A at the
standard rating points according to EN 12900.
- A-weighted sound power level LWA (re 1 pW), in decibel. To
determine the values, measurement methods of the ISO 3740 standard with
accuracy class 2 or higher were used .
- A-weighted sound pressure level LpA (re 20 µPa), in decibel.
The values are calculated from the sound power level in accordance with ISO
11203: LpA = LWA - Q2 at a distance of d = 1m
to the reference box.
|
6) | Only with additional
adapter possible |
7) | Mounted |
8) | Enclosure |
9) | Enclosure (screw-in part mounted) |
10) | On request |