Semi-hermetic air-cooled reciprocating compressor in compact design. The
suction gas is not heated up by the motor, but rather drawn in directly from the
compressor. The motor is cooled by means of a compact, integrated ventilation
unit, which cools not only the motor, but also the compressor and in particular
the cylinder heads, by means of targeted air cooling. The best possible
serviceability is provided by means of a replaceable drive motor, among other
things. The compressor stands out due to its outstanding running comfort and
efficient operating performance. Dependable mechanism lubrication is guaranteed
by means of an oil pump which is independent of rotating direction, as well as a
large-volume oil sump. An electronic motor protection uses PTC sensors in series
to monitor the winding temperature and, if desired, the discharge gas
temperature.
Colour: blue (RAL 5000)
Technical data
HAX34e/255-4
Application | Refrigeration & AC |
Compressor refrigeration capacity | 3.76 kW |
Power consumption | 2.74 kW |
Current draw (400 V) | 5.31 A |
Mass flow | 0.028 kg/s |
at following operating condition:
Refrigerant | R404A, R507 |
Reference temperature | Dew point |
Evaporating temperature | -35.0 °C |
Condensing temperature | 40.0 °C |
Supply frequency | 50 Hz |
Voltage | 400 V |
Suction gas temperature | 20 °C |
Subcooling (outside cond.) | 0 K |
Number of cylinders / Bore / Stroke | 4 / 45 mm / 40 mm |
Displacement 50/60 Hz (1450/1740 ¹/min) | 22,10 / 26,60 m³/h |
Voltage 1) | 220-240V Δ / 380-420V Y -3- 50Hz |
| 265-290V Δ / 440-480V Y -3- 60Hz |
Max. working current 2) | 13.8 / 8.0 A |
Max. power consumption 2) | 4.7 kW |
Starting current (rotor blocked) 2) | 87.0 / 50.0 A |
Motor protection | INT69 G |
Protection terminal box / HA-fan | IP 66 / IP 44 |
Voltage HA-fan | 230 V - 1 - 50/60 Hz, 38 W |
Weight | 93 kg |
Frequency range 3) | 25 - 70 Hz |
Max. permissible overpressure (g) (LP/HP) 4) | 19 / 28 bar |
Connection suction line SV | 22 mm - 7/8 " |
Connection discharge line DV | 16 mm - 5/8 " |
Lubrication | Oil pump |
Oil type R134a, R404A, R407A/C/F, R448A, R449A, R450A, R513A | BOCKlub E55 |
Oil type R22 | BOCKlub A46 |
Oil charge | 1,3 Ltr. |
Dimensions
Length / Width / Height | 578 / 303 / 318 mm |
Scope of supply
Semi-hermetic four
cylinder reciprocating compressor with drive motor
Single-section compressor housing with hermetically integrated electric
motor
Winding protection with PTC resistor sensors and
electronic trigger unit INT69 G
115-230 V AC, 50/60 Hz,
IP00
Motor is cooled by an integrated ventilator with air
deflection hood.
230 V - 1 - 50/60 Hz, 38 W, 0,17 A
Oil pump
Possibility for connection of oil pressure safety switch
MP55
Possibility of
connection of oil level controllers ESK, Traxoil, AC+R or CARLY 5)
Oil charge:
HA: BOCKlub A46
HAX:
BOCKlub E55
Sight glass
Suction and discharge line valve
Inert gas charge
Accessories
Digital capacity regulator DCR14 230 V - 1 - 50/60
Hz, IP65
1 digital capacity regulator = 50% residual capacity
Cylinder cover prepared for digital capacity regulator
Oil sump heater
110-240 V - 1 - 50/60 Hz, 50-120 W, IP66
PTC heater
self-regulating
USB converter for INT69 G Diagnose 6)
Oil pressure safety switch MP55 230 V - 1 - 50/60 Hz,
IP20 6)
Thermal protection thermostat per cylinder cover
7)
INT69 G Diagnose 115-230 V AC, 50/60 Hz, IP00 (INT69 G
not applicable)
DP-Modbus Gateway 115-230 V AC, 50/60 Hz, IP00 including
adapter cable 6)
Modbus-LAN Gateway 230 V AC, 50/60 Hz,
IP00 6)
Step protection
4 anti-vibration pads enclosed
Special voltage and/or frequency (on request)
Notes
1) | Tolerance (± 10%)
relates to the mean value of the voltage range. Other voltages and current types
on request
All data are based on voltage rms values |
2) | - The stated value for the max. power consumption is valid
for the adjusted power supply.
- Starting current (rotor blocked):
- Part winding (PW) motors: Winding 1 / Winding 1+2
- Delta/Star (Δ/Y) motors: Δ / Y
- Take account of the max.
operating current / max. power consumption for designing motor contractors, feed
lines, fuses and motor protection switches. Motor contractors: Consumption
category AC3. |
3) | The maximum permissible working current of the compressor
(Imax) must not be exceeded. Take account of the guidelines for use of frequency
inverter (see compressor assembly instruction or selection software).
|
4) | LP = Low
pressure HP = High pressure |
5) | Only with additional
adapter possible |
6) | Enclosure |
7) | Mounted |