Compressor mounted on a horizontal receiver. Semi-hermetic suction gas-cooled
reciprocating compressor in compact design. The best possible serviceability is
provided by means of a replaceable drive motor, among other things. The
compressor stands out due to its outstanding running comfort and efficient
operating performance. The suction shut-off valve can be rotated by 90° in each
instance. Dependable mechanism lubrication is guaranteed by means of an oil pump
which is independent of rotating direction, as well as a large-volume oil sump.
The large-volume electric terminal box (IP65) in solid aluminium design has a
fold-back and removable hinged lid with easy quick-release fastener. An
electronic motor protection MP10 with optical status indication uses PTC sensors
in series to monitor the winding temperature and, if desired, the discharge gas
temperature.
Colour: blue (RAL 5000)
Technical data
SHGX12P/110-4 RU
Application | Refrigeration & AC |
Compressor refrigeration capacity | 4.73 kW |
Power consumption | 1.59 kW |
Current draw (400 V) | 3.23 A |
Mass flow | 0.033 kg/s |
at following operating condition:
Refrigerant | R134a |
Reference temperature | Dew point |
Evaporating temperature | 5.0 °C |
Condensing temperature | 50.0 °C |
Supply frequency | 50 Hz |
Voltage | 400 V |
Suction gas temperature | 20 °C |
Subcooling (outside cond.) | 0 K |
Number of cylinders / Bore / Stroke | 2 / 45 mm / 34 mm |
Displacement 50/60 Hz (1450/1740 ¹/min) | 9,40 / 11,30 m³/h |
Voltage 1) | 220-240V Δ / 380-420V Y -3- 50Hz |
| 265-290V Δ / 440-480V Y -3- 60Hz |
Max. working current 2) | 9.2 / 5.3 A |
Max. power consumption 2) | 3.1 kW |
Starting current (rotor blocked) 2) | 43.0 / 25.0 A |
Motor protection | MP10 |
Protection terminal box | IP 66 |
Weight | 58 kg |
Max. permissible overpressure (g) (LP/HP) 3) | 19 / 28 bar |
Connection suction line SV | 16 mm - 5/8 " |
Connection discharge line DV | 12 mm - 1/2 " |
Connection liqiud outlet line FLA | 10 mm - 3/8 " |
Lubrication | Oil pump |
Oil type R134a, R404A, R407A/C/F, R448A, R449A, R450A, R513A | BOCKlub E55 |
Oil type R22 | BOCKlub A46 |
Oil charge | 0,8 Ltr. |
Dimensions
Length / Width / Height | 480 / 260 / 450 mm |
Receiver content | 5,3 Ltr. |
Max. refrigerant charge
R134a 4) | 5,8 kg |
R404A / R507 4) | 5,1 kg |
R407C / R407F 4) | 5,5 / 5,4 kg |
R22 4) | 5,8 kg |
Scope of supply
HG P or HG e semi-hermetic motor compressor (Extent of delivery see compressor) installed with rubber anti-vibration pads on liquide receiver. The liquid receivers with sight glass and Rotalock shut-off valve with brazing connection. Tank is provided (appropriate pressure appliance guideline)
Oil pump
4 rubber slabs enclosed for installation of the compressor unit
Accessories
Progressively adjustable speed control by means of an
EFC (Electronic Frequency Control),
compactly built onto compressor and
connected ready-to-operate
HA/HG12P: IP65
HA22P/HG22e, HA34P/HG34e: IP54
Oil sump heater
110-240 V - 1 - 50/60 Hz, 50-120 W, IP66
PTC heater
self-regulating
Thermal protection thermostat
Oil pressure safety switch MP55 230 V - 1 - 50/60 Hz,
IP20 5)
Additional fan
230 V AC - 1 - 50 Hz, 72 W, IP44
230 V AC - 1 - 60
Hz, 68 W
5)High pressure safety limiter + controller/ +low pressure
controller
Oil separator incl. mounting
Special voltage and/or frequency (on request)
Notes
1) | Tolerance (± 10%)
relates to the mean value of the voltage range. Other voltages and current types
on request
All data are based on voltage rms values |
2) | - The stated value for the max. power consumption is valid
for the adjusted power supply.
- Starting current (rotor blocked):
- Part winding (PW) motors: Winding 1 / Winding 1+2
- Delta/Star (Δ/Y) motors: Δ / Y
- Take account of the max.
operating current / max. power consumption for designing motor contractors, feed
lines, fuses and motor protection switches. Motor contractors: Consumption
category AC3. |
3) | LP = Low
pressure HP = High pressure |
4) | With liquide temperature at 20°C and 90 % capacity |
5) | Enclosure |