Scope of supply and accessories |
|
Scope of supply and accessories |
|
|
Dimensions and connections |
|
Dimensions and connections |
|
| | |
|
Spare part list, drawings & downloads |
|
Spare part list, drawings & downloads |
|
| | |
|
|
| |
| |
|
|
Unlimited application range
Supplementary cooling or reduced suction gas temperature (Δtoh<20K)
Compressor operation is possible within the limits shown
on the diagrams of application. Please note the coloured areas. Compressor
application limits should not be chosen for design purposes or continuous
operation. Axis values refer to dew point (saturated vapour line).
Number of cylinders / Bore / Stroke |
4 / 50 mm / 40 mm |
Displacement 50 Hz (1450 ¹/min) |
27,30 m³/h |
Voltage |
220-240V Δ / 380-420V Y -3- 50Hz |
Max. working current |
21.1 / 12.2 A |
Max. power consumption |
7.4 kW |
Starting current (rotor blocked) |
111.0 / 64.0 A |
Motor protection |
MP10 |
Protection terminal box |
IP 66 |
Weight |
198 kg |
Max. permissible overpressure (g) (LP/HP) |
19 / 28 bar |
Connection suction line SV |
28 mm - 1 1/8 " |
Connection liqiud outlet line FLA |
12 mm - 1/2 " |
Lubrication |
Oil pump |
Oil type R134a, R404A, R407A/C/F, R448A, R449A, R450A, R513A |
BOCKlub E55 |
Oil type R22 |
BOCKlub A46 |
Oil charge |
1,3 Ltr. |
Dimensions
Length / Width / Height |
1600 / 700 / 1000 mm |
Number fan motors |
1 |
Voltage |
230 V - 1 - 50 Hz |
Max. working current 50 Hz |
1 x 2,60 A |
Max. power consumption 50 Hz |
1 x 600 W |
Air flow 50 Hz |
7895 m³/h |
Receiver content |
8,0 Ltr. |
Volume condenser |
6,2 Ltr. |
Dimensioned drawing | display with dimensions and connections |
Format: PDF |
Download |
|
SV |
Suction line valve, tube ø |
28 mm - 1 1/8 " |
FLA |
Liquid outlet, tube ø |
12 mm - 1/2 " |
SI |
Connection safety valve |
1/2" NPTF |
Y1 |
Connection liquid side, lockable |
7/16" UNF |
Y2 |
Connection liquid side, not lockable |
7/16" UNF |
Y3 |
Connection for Schrader valve speed control for the fan |
7/16" UNF |
Confirm the license rules | |
|
|
| |
|
|
High-resolution disaggregated component drawing/display of position |
Format: PDF |
Download |
Spare parts list (up to DK 056) |
Format: PDF |
Download |
Dimensioned drawing | display with dimensions and connections |
Format: PDF |
Download |
Product drawing | Display without dimensions |
Format: DWG |
Download |
Product drawing | Display without dimensions |
Format: DXF |
Download |
Assembly instructions Plusbox |
Format: PDF |
German English French |
Pressure Vessel Directive |
Format: PDF |
German English French |
Technical dataSHGX34e/315-4 PB Application | Refrigeration & AC | Compressor refrigeration capacity | 15.30 kW | Power consumption | 5.02 kW 1) | Current draw (400 V) | 7.97 A | Mass flow | 0.101 kg/s |
at following operating condition: Refrigerant | R134a | Reference temperature | Dew point | Evaporating temperature | 5.0 °C | Condensing temperature | 47.4 °C | Air inlet temperature | 32.0 °C | Supply frequency | 50 Hz | Voltage | 400 V | Suction gas temperature | 20 °C | Subcooling (outside cond.) | 3 K |
Number of cylinders / Bore / Stroke | 4 / 50 mm / 40 mm | Displacement 50 Hz (1450 ¹/min) | 27,30 m³/h | Voltage 2) | 220-240V Δ / 380-420V Y -3- 50Hz | Max. working current 3) | 21.1 / 12.2 A | Max. power consumption 3) | 7.4 kW | Starting current (rotor blocked) 3) | 111.0 / 64.0 A | Motor protection | MP10 | Protection terminal box | IP 66 | Weight | 198 kg | Max. permissible overpressure (g) (LP/HP) 4) | 19 / 28 bar | Connection suction line SV | 28 mm - 1 1/8 " | Connection liqiud outlet line FLA | 12 mm - 1/2 " | Lubrication | Oil pump | Oil type R134a, R404A, R407A/C/F, R448A, R449A, R450A, R513A | BOCKlub E55 | Oil type R22 | BOCKlub A46 | Oil charge | 1,3 Ltr. | Dimensions
Length / Width / Height | 1600 / 700 / 1000 mm | Number fan motors | 1 | Voltage | 230 V - 1 - 50 Hz | Max. working current 50 Hz | 1 x 2,60 A | Max. power consumption 50 Hz | 1 x 600 W | Air flow 50 Hz | 7895 m³/h | Receiver content | 8,0 Ltr. | Volume condenser | 6,2 Ltr. |
Scope of supplyInformation about the scope of supply is available in our
Plusbox configurator on http://vap.bock.de/plusbox/en
AccessoriesInformation about accessories is available in our Plusbox
configurator on http://vap.bock.de/plusbox/en
Notes1) | Power consumption of condenser fans included.
| 2) | Tolerance (± 10%)
relates to the mean value of the voltage range. Other voltages and current types
on request
All data are based on voltage rms values | 3) | - The stated value for the max. power consumption is valid
for the adjusted power supply.
- Starting current (rotor blocked):
- Part winding (PW) motors: Winding 1 / Winding 1+2
- Delta/Star (Δ/Y) motors: Δ / Y
- Take account of the max.
operating current / max. power consumption for designing motor contractors, feed
lines, fuses and motor protection switches. Motor contractors: Consumption
category AC3. | 4) | LP = Low
pressure HP = High pressure |
|