Air-cooled condensation unit with large-dimensioned condensers, optimised
closed loops and heat transfer in conjunction with high-power fans. These
cost-effective fans with thermal protection shield are well-suited for
electronic speed regulation for an optimal condensation pressure setting.
Semi-hermetic, suction gas-cooled 4-cylinder reciprocating compressor in
compact design. The best possible serviceability is provided by means of a
replaceable drive unit, among other things. The compressor stands out due to its
outstanding running comfort and efficient operating performance. The suction
shut-off valve can be rotated by 90° in each instance. Dependable mechanism
lubrication is guaranteed by means of an oil pump which is independent of
rotating direction, as well as a large-volume oil sump. The optional oil sump
heating is carried out using an immersion sleeve and can therefore be replaced
without intervening in the refrigeration cycle.
An additional connection facility for an oil level regulator is available as
a standard. The electrical connection is simplified by means of a large-volume
electric terminal box. The electronic motor protection MP10 with optical status
indication uses PTC sensors in series to monitor the winding temperature and, if
desired, the discharge gas temperature.
Colour: blue (RAL 5000)
Technical data
SHGX4/465-4 SL
Application | Refrigeration & AC |
Compressor refrigeration capacity | 24.80 kW |
Power consumption | 8.54 kW 1) |
Current draw (400 V) | 13.10 A |
Mass flow | 0.156 kg/s |
at following operating condition:
Refrigerant | R134a |
Reference temperature | Dew point |
Evaporating temperature | 5.0 °C |
Condensing temperature | 42.5 °C |
Air inlet temperature | 32.0 °C |
Supply frequency | 50 Hz |
Voltage | 400 V |
Suction gas temperature | 20 °C |
Subcooling (outside cond.) | 3 K |
Number of cylinders / Bore / Stroke | 4 / 55 mm / 49 mm |
Displacement 50/60 Hz (1450/1740 ¹/min) | 40,50 / 48,60 m³/h |
Voltage 2) | 380-420V Y/YY -3- 50Hz PW |
| 440-480V Y/YY -3- 60Hz PW |
Winding divided into | 66% / 33% |
Max. working current 3) | 25.0 A |
Max. power consumption 3) | 14.2 kW |
Starting current (rotor blocked) 3) | 82.0 / 107.0 A |
Motor protection | MP10 |
Protection terminal box | IP 65 |
Weight | 292 kg |
Max. permissible overpressure (g) (LP/HP) 4) | 19 / 28 bar |
Connection suction line SV | 35 mm - 1 3/8 " |
Connection liqiud outlet line FLA | 16 mm - 5/8 " |
Lubrication | Oil pump |
Oil type R134a, R404A, R407A/C/F, R448A, R449A, R450A, R513A | BOCKlub E55 |
Oil type R22 | BOCKlub A46 |
Oil charge | 2,7 Ltr. |
Oil sump heater | 230 V - 1 - 50/60 Hz, 80 W |
Dimensions of unit
Length / Width / Height | 1300 / 890 / 1310 mm |
Number fan motors | 4 |
Voltage | 230 V - 1 - 50/60 Hz |
Max. working current 50/60 Hz | 4 x 2,50 / 3,30 A |
Max. power consumption 50/60 Hz | 4 x 500 / 710 W |
Air flow 50/60 Hz | 16280 / 17340 m³/h |
Receiver content | 14.00 Ltr. |
Max. refrigerant charge
R134a 5) | 15,5 kg |
R404A / R507 5) | 13,5 kg |
R407C / R407F 5) | 14,6 / 14,3 kg |
R22 5) | 15,3 kg |
Volume condenser | 15,4 Ltr. |
Scope of supply
HG or HGX semi-hermetic motor compressor (Extent of
delivery see compressor) installed with rubber anti-vibration pads on liquide
receiver. The liquid receivers with sight glass and Rotalock shut-off valve with
brazing connection. Tank is provided (appropriate pressure appliance guideline)
Oil pump
Air-cooled finned tube condenser with 4
ventilators:
- Ventilators 230 V - 1 - 50/60 Hz, with bimetal winding
protection, phase control for speed adjustment (regulator not included in scope
of supplies)
- With piping on discharge and liquide side. Service charge
4 rubber plates enclosed for installation of the condensing unit
Accessories
Start unloader 230 V - 1 - 50/60 Hz, IP65, less check valve,
including
thermal protection thermostat (posistor tracer)
Start unloader by means of a ESS (Electronic Soft
Start), 400 V - 3 - 50/60 Hz, IP20 (Connection clamps IP00) for installation in
switch cabinet 6)
Capacity regulator 230 V - 1 - 50/60 Hz, IP65
1 capacity regulator = 50% residual capacity
Oil sump heater 230 V - 1 - 50/60 Hz, 80 W
Oil service valve
Oil pressure safety switch MP54 230 V - 1 - 50/60 Hz,
IP20 6)
Oil differential pressure sensor DELTA-P II 220-240 V -
1 - 50/60 Hz 6)
Water-cooled cylinder covers
Thermal protection thermostat per cylinder cover
Sea water resistant water-cooled cylinder covers
Additional fan
230 V AC - 1 - 50 Hz, 97 W,
IP44
230 V AC - 1 - 60 Hz, 128 W 6)
High pressure safety limiter + controller/ +low pressure
controller
Safety valve for receiver 7)
Instrument panel with gauges for high, low and oil pressure incl. mounting
Oil separator incl. mounting
Ventilators 230 V D / 400 V Y - 3 - 50/60 Hz
Special voltage and/or frequency (on request)
Notes
1) | Power consumption of condenser fans included.
|
2) | Tolerance (± 10%)
relates to the mean value of the voltage range. Other voltages and current types
on request
All data are based on voltage rms values
PW = part
winding, motors for part winding starting (no start unloaders required)
Designs for Y/D on request |
3) | - The stated value for the max. power consumption is valid
for the adjusted power supply.
- Starting current (rotor blocked):
- Part winding (PW) motors: Winding 1 / Winding 1+2
- Delta/Star (Δ/Y) motors: Δ / Y
- Take account of the max.
operating current / max. power consumption for designing motor contractors, feed
lines, fuses and motor protection switches. Motor contractors: Consumption
category AC3. |
4) | LP = Low
pressure HP = High pressure |
5) | With liquide temperature at 20°C and 90 % capacity |
6) | Enclosure |
7) | Mounted |