Air-cooled condensation unit with large-dimensioned condensers, optimised
closed loops and heat transfer in conjunction with high-power fans. These
cost-effective fans with thermal protection shield are well-suited for
electronic speed regulation for an optimal condensation pressure
setting.
Semi-hermetic suction gas-cooled reciprocating compressor in
compact design. The best possible serviceability is provided by means of a
replaceable drive motor, among other things. The compressor stands out due to
its outstanding running comfort and efficient operating performance. The suction
shut-off valve can be rotated by 90° in each instance. Dependable mechanism
lubrication is guaranteed by means of an oil pump which is independent of
rotating direction, as well as a large-volume oil sump. An electronic motor
protection uses PTC sensors in series to monitor the winding temperature and, if
desired, the discharge gas temperature.
Colour: blue (RAL
5000)
Technical data
SHGX34e/315-4 L
Application | Refrigeration & AC |
Compressor refrigeration capacity | 15.10 kW |
Power consumption | 5.04 kW 1) |
Current draw (400 V) | 8.02 A |
Mass flow | 0.100 kg/s |
at following operating condition:
Refrigerant | R134a |
Reference temperature | Dew point |
Evaporating temperature | 5.0 °C |
Condensing temperature | 48.2 °C |
Air inlet temperature | 32.0 °C |
Supply frequency | 50 Hz |
Voltage | 400 V |
Suction gas temperature | 20 °C |
Subcooling (outside cond.) | 3 K |
Number of cylinders / Bore / Stroke | 4 / 50 mm / 40 mm |
Displacement 50/60 Hz (1450/1740 ¹/min) | 27,30 / 32,80 m³/h |
Voltage 2) | 220-240V Δ / 380-420V Y -3- 50Hz |
| 265-290V Δ / 440-480V Y -3- 60Hz |
Max. working current 3) | 21.1 / 12.2 A |
Max. power consumption 3) | 7.4 kW |
Starting current (rotor blocked) 3) | 111.0 / 64.0 A |
Motor protection | INT69 G |
Protection terminal box | IP 66 |
Weight | 169 kg |
Max. permissible overpressure (g) (LP/HP) 4) | 19 / 28 bar |
Connection suction line SV | 28 mm - 1 1/8 " |
Connection liqiud outlet line FLA | 12 mm - 1/2 " |
Lubrication | Oil pump |
Oil type R134a, R404A, R407A/C/F, R448A, R449A, R450A, R513A | BOCKlub E55 |
Oil type R22 | BOCKlub A46 |
Oil charge | 1,3 Ltr. |
Dimensions
Length / Width / Height | 1085 / 650 / 745 mm |
Number fan motors | 1 |
Voltage | 230 V - 1 - 50/60 Hz |
Max. working current 50/60 Hz | 1 x 2,50 / 3,20 A |
Max. power consumption 50/60 Hz | 1 x 580 / 730 W |
Air flow 50/60 Hz | 5950 / 5870 m³/h |
Receiver content | 8.0 Ltr. |
Max. refrigerant charge
R134a 5) | 8,8 kg |
R404A / R507 5) | 7,7 kg |
R407C / R407F 5) | 8,3 / 8,2 kg |
R22 5) | 8,7 kg |
Volume condenser | 6,3 Ltr. |
Scope of supply
HG P or HG
e semi-hermetic motor compressor (Extent of delivery see compressor)
installed on the unit with anti-vibration pads. The liquid receivers with sight
glass and Rotalock shut-off valve with brazing connection. Tank is provided
(appropriate pressure appliance guideline)
Oil pump
Air-cooled finned tube condenser with 1 ventilator:
-
Ventilator 230 V - 1 - 50/60 Hz, with bimetal winding protection, phase control
for speed adjustment (speed regulator not included in scope of supplies)
-
With piping on discharge and liquide side. Service charge
4 rubber plates enclosed for installation of the condensing unit
Accessories
Start unloader by means of a ESS (Electronic Soft
Start), 400 V - 3 - 50/60 Hz, IP20 (Connection clamps IP00) for installation in
switch cabinet 6)
Capacity regulator 230 V - 1 - 50/60 Hz, IP65
1 capacity regulator = 50% residual capacity
Cylinder cover prepared for capacity regulator
Oil sump heater
110-240 V - 1 - 50/60 Hz, 50-120 W, IP66
PTC heater
self-regulating
Thermal protection thermostat
Oil pressure safety switch MP55 230 V - 1 - 50/60 Hz,
IP20 6)
Additional fan
230 V AC - 1 - 50 Hz, 97 W,
IP44
230 V AC - 1 - 60 Hz, 128 W 6)
High pressure safety limiter + controller/ +low pressure
controller 7)
Oil separator incl. mounting
Waterproof housing 6)
Speed controll for the ventilator 6)
Ventilators 230 V D / 400 V Y - 3 - 50/60 Hz
Further accessory parts see compressor
Notes
1) | Power consumption of condenser fans included.
|
2) | Tolerance (± 10%)
relates to the mean value of the voltage range. Other voltages and current types
on request
All data are based on voltage rms values |
3) | - The stated value for the max. power consumption is valid
for the adjusted power supply.
- Starting current (rotor blocked):
- Part winding (PW) motors: Winding 1 / Winding 1+2
- Delta/Star (Δ/Y) motors: Δ / Y
- Take account of the max.
operating current / max. power consumption for designing motor contractors, feed
lines, fuses and motor protection switches. Motor contractors: Consumption
category AC3. |
4) | LP = Low
pressure HP = High pressure |
5) | With liquide temperature at 20°C and 90 % capacity |
6) | Enclosure |
7) | Mounted |