Technical data
HGX34P/315-4 R410A
Application | Refrigeration & AC |
Compressor refrigeration capacity | 18.50 kW |
Power consumption | 8.34 kW |
Current draw (400 V) | 14.00 A |
Mass flow | 0.108 kg/s |
at following operating condition:
Refrigerant | R410A |
Reference temperature | Dew point |
Evaporating temperature | -10.0 °C |
Condensing temperature | 45.0 °C |
Supply frequency | 50 Hz |
Voltage | 400 V |
Suction gas temperature | 20 °C |
Subcooling (outside cond.) | 0 K |
Number of cylinders / Bore / Stroke | 4 / 50 mm / 40 mm |
Displacement 50/60 Hz (1450/1740 ¹/min) | 27,30 / 32,80 m³/h |
Voltage 1) | 220-240V Δ / 380-420V Y -3- 50Hz |
| 265-290V Δ / 440-480V Y -3- 60Hz |
Max. working current 2) | 30.5 / 17.6 A |
Max. power consumption 2) | 10.1 kW |
Starting current (rotor blocked) 2) | 132.0 / 76.0 A |
Motor protection | MP10 |
Protection terminal box | IP 66 |
Weight | 97 kg |
Max. permissible overpressure (g) (LP/HP) 3) | 27 / 43 bar |
Connection suction line SV | 28 mm - 1 1/8 " |
Connection discharge line DV | 22 mm - 7/8 " |
Lubrication | Oil pump |
Oil type R410A | BOCKlub E55 |
Oil charge | 1,3 Ltr. |
Dimensions
Length / Width / Height | 515 / 285 / 315 mm |
Scope of supply
Semi-hermetic four
cylinder reciprocating compressor with drive motor
Single-section compressor housing with hermetically integrated electric
motor
Winding protection with PTC resistor sensors and
electronic trigger unit MP 10
Possibility of
connection of oil level controllers ESK, Traxoil, AC+R or CARLY 4)
Oil sump
heater
110-240 V - 1 - 50/60 Hz, 50-120 W
PTC heater
self-regulating
Oil charge:
BOCKlub E55
Sight glass
Suction and discharge line valve
Thermal protective thermostat (posistor tracer)
Inert gas charge
4 anti-vibration pads enclosed
Accessories
Start unloader by means of a ESS (Electronic Soft
Start), 400 V - 3 - 50/60 Hz, IP20 (Connection clamps IP00) for installation in
switch cabinet
Progressively adjustable speed control by means of an
EFC (Electronic Frequency Control),
compactly built onto compressor and
connected ready-to-operate
HA/HG12P: IP65
HA22P/HG22e, HA34P/HG34e: IP54
Compressor oil Bock C 55 E as 1 or 5 liter refill unit
Additional fan
230 V AC - 1 - 50 Hz, 97 W,
IP44
230 V AC - 1 - 60 Hz, 128 W
Special voltage and/or frequency (on request)
Notes
1) | Tolerance (± 10%)
relates to the mean value of the voltage range. Other voltages and current types
on request
All data are based on voltage rms values |
2) | - The stated value for the max. power consumption is valid
for the adjusted power supply.
- Starting current (rotor blocked):
- Part winding (PW) motors: Winding 1 / Winding 1+2
- Delta/Star (Δ/Y) motors: Δ / Y
- Take account of the max.
operating current / max. power consumption for designing motor contractors, feed
lines, fuses and motor protection switches. Motor contractors: Consumption
category AC3. |
3) | LP = Low
pressure HP = High pressure |
4) | Only with additional
adapter possible |