Open type piston compressor for external drive. The compressor design is very
compact and robust. Dependable mechanism lubrication is guaranteed by means of
an oil pump which is independent of rotating direction, as well as a
large-volume oil sump.
Colour: blue (RAL 5000)
Technical data
FX16/2051
Application | Refrigeration & AC |
Compressor refrigeration capacity | 89.90 kW |
Drive power | 26.40 kW |
Torque | 175.00 Nm |
Mass flow | 0.629 kg/s |
at following operating condition:
Refrigerant | R134a |
Reference temperature | Dew point |
Evaporating temperature | 5.0 °C |
Condensing temperature | 50.0 °C |
Speed | 1450 1/min |
Suction gas temperature | 20 °C |
Subcooling (outside cond.) | 0 K |
Number of cylinders / Bore / Stroke | 6 / 80 mm / 68 mm |
Displacement (1450/1740 ¹/min) | 178,40 / 214,10 m³/h |
Mass moment of inertia | 0,0390 kgm² |
Weight | 175 kg |
Permissible range of rotation speeds | 700 - 1800 ¹/min |
Max. permissible overpressure (g) (LP/HP) 1) | 19 / 28 bar |
Connection suction line SV | 54 mm - 2 1/8 " |
Connection discharge line DV | 42 mm - 1 5/8 " |
Lubrication | Oil pump |
Oil type R134a, R404A, R407A/C/F, R448A, R449A, R450A, R513A | BOCKlub E55 |
Oil type R22 | BOCKlub A46 |
Oil charge | 5,0 Ltr. |
Oil sump heater | 230 V - 1 - 50/60 Hz, 140 W |
Oil service valve | 7/16" UNF |
Dimensions
Length / Width / Height | 580 / 515 / 535 mm |
Scope of supply
Open piston
compressor
with suction and pressure shutoff valves
Oil pump
Six cylinder, cylinder arrangement in W
Seat front bearing
flange
Shaft seal with piece of tube for controlled oil collection
Possibility of
connection of oil level controllers ESK, AC+R or CARLY 2)
Oil pump cover with screw-in option for oil differential
pressure sensor DELTA-P II
Oil charge:
F: BOCKlub A46
FX: BOCKlub
E55
Sight glass
Pressure relief valve
Inert gas charge
Accessories
Capacity regulator 230 V - 1 - 50/60 Hz, IP65
1-2
capacity regulator = 66/33% residual capacity
Flywheel:
Outer
diameter: 322,5 [mm]
V-belt profile: SPB DIN 7753
Number of grooves:
5
Weight: 20,0 [kg] 3)
Shaft coupling for direct drive (enclosure) 4)
Oil sump heater 230 V - 1 - 50/60 Hz, 140 W
Oil service valve
Oil pressure safety switch MP54 230 V - 1 - 50/60 Hz,
IP20 3)
Oil differential pressure sensor DELTA-P II 220-240 V -
1 - 50/60 Hz 3)
Thermal protection thermostat (bimetal tracer)
Two additional sight
glasses (both sides)
Elevated base plate: additional 2.5 Ltr. oil charge and 8
kg additional weight
Notes
1) | LP = Low
pressure HP = High pressure |
2) | Only with additional
adapter possible |
3) | Enclosure |
4) | Please state motor Ø and feather key groove dimensions
when ordering shafts |