Semi-hermetic, suction gas-cooled 4-cylinder reciprocating compressor in
compact design. The best possible serviceability is provided by means of a
replaceable drive unit, among other things. The compressor stands out due to its
outstanding running comfort and efficient operating performance. The suction
shut-off valve can be rotated by 90° in each instance. Dependable mechanism
lubrication is guaranteed by means of an oil pump which is independent of
rotating direction, as well as a large-volume oil sump. The optional oil sump
heating is using an immersion sleeve and can therefore be replaced without
intervening in the refrigeration cycle.
An additional connection facility for an oil level regulator is available as
a standard. The electrical connection is simplified by means of a large-volume
electric terminal box. The electronic motor protection INT69 G uses PTC sensors
in series to monitor the winding temperature and, if desired, the discharge gas
temperature.
Color: blue (RAL 5000)
Technical data
HGX44e/770-4 S
Application | Refrigeration & AC |
Compressor refrigeration capacity | 36.30 kW |
Power consumption | 10.70 kW |
Current draw (400 V) | 19.60 A |
Mass flow | 0.254 kg/s |
at following operating condition:
Refrigerant | R134a |
Reference temperature | Dew point |
Evaporating temperature | 5.0 °C |
Condensing temperature | 50.0 °C |
Supply frequency | 50 Hz |
Voltage | 400 V |
Suction gas temperature | 20 °C |
Subcooling (outside cond.) | 0 K |
Number of cylinders / Bore / Stroke | 4 / 70 mm / 50 mm |
Displacement 50/60 Hz (1450/1740 ¹/min) | 67,00 / 80,40 m³/h |
Voltage 1) | 380-420V Y/YY -3- 50Hz PW |
| 440-480V Y/YY -3- 60Hz PW |
Winding divided into | 70% / 30% |
Max. working current 2) | 35.0 A |
Max. power consumption 2) | 21.4 kW |
Starting current (rotor blocked) 2) | 133.0 / 171.0 A |
Motor protection | INT69 G |
Protection terminal box | IP 65 |
Weight | 168 kg |
Max. permissible overpressure (g) (LP/HP) 3) | 19 / 28 bar |
Connection suction line SV | 42 mm - 1 5/8 " |
Connection discharge line DV | 28 mm - 1 1/8 " |
Lubrication | Oil pump |
Oil type R134a, R404A, R407A/C/F, R448A, R449A, R450A, R513A | BOCKlub E55 |
Oil type R22 | BOCKlub A46 |
Oil charge | 2,3 Ltr. |
Oil sump heater | 230 V - 1 - 50/60 Hz, 160 W |
Dimensions
Length / Width / Height | 695 / 360 / 385 mm |
Scope of supply
Semi-hermetic four-cylinder reciprocating compressor
with drive motor
Single-section compressor housing with hermetically integrated electric motor
Winding protection with PTC resistor sensors and
electronic trigger unit INT69 G
115-230 V AC, 50/60 Hz,
IP00
Oil pump
Possibility of
connection of oil level controllers ESK, AC+R or CARLY
Possibility of connection of oil level controllers Traxoil 4)
Possibility for connection of oil pressure safety switch
MP54
Oil charge:
HG: BOCKlub A46
HGX:
BOCKlub E55
Sight glass
Pressure relief valve
Suction and discharge line valve
Inert gas charge
4 anti-vibration pads enclosed
Accessories
Start unloader by means of a ESS (Electronic Soft
Start), 400 V - 3 - 50/60 Hz, IP20 (Connection clamps IP00) for installation in
switch cabinet 5)
Capacity regulator 230 V - 1 - 50/60 Hz, IP65
1 capacity regulator = 50% residual capacity
Cylinder cover prepared for capacity regulator
Oil sump heater 230 V - 1 - 50/60 Hz, 160
W
Thermal protection thermostat per compressors 2x
possible
USB converter for INT69 G Diagnose 5)
Oil service valve
Intermediate flange for discharge line valve on right or
left seen from oil pump
Oil pressure safety switch MP54 230 V - 1 - 50/60 Hz,
IP20 5)
Connection piece suction and discharge valve in welding
design
Oil differential pressure sensor DELTA-P II 220-240 V -
1 - 50/60 Hz 6)
Oil temperature sensor (Pt1000, for external evaluation)
5)
Rear bearing flange prepared for oil differential
pressure sensor DELTA-P II
INT69 G Diagnose 115-230 V AC, 50/60 Hz, IP00 (INT69 G
not applicable)
DP-Modbus Gateway 115-230 V AC, 50/60 Hz, IP00 including
adapter cable 5)
Modbus-LAN Gateway 230 V AC, 50/60 Hz,
IP00 5)
Additional fan
230 V AC - 1 - 50 Hz, 97 W,
IP44
230 V AC - 1 - 60 Hz, 128 W 5)
Special voltage and/or frequency (on request)
Notes
1) | Tolerance (± 10%)
relates to the mean value of the voltage range. Other voltages and current types
on request
All data are based on voltage rms values
PW = part
winding, motors for part winding starting (no start unloaders required)
Designs for Y/D on request |
2) | - The stated value for the max. power consumption is valid
for the adjusted power supply.
- Starting current (rotor blocked):
- Part winding (PW) motors: Winding 1 / Winding 1+2
- Delta/Star (Δ/Y) motors: Δ / Y
- Take account of the max.
operating current / max. power consumption for designing motor contractors, feed
lines, fuses and motor protection switches. Motor contractors: Consumption
category AC3. |
3) | LP = Low
pressure HP = High pressure |
4) | Only with additional
adapter possible |
5) | Enclosure |
6) | Enclosure (screw-in part mounted) |