Semi-hermetic air-cooled reciprocating compressor in compact design. The
suction gas is not heated up by the motor, but rather drawn in directly from the
compressor. The motor is cooled by means of a compact, integrated ventilation
unit, which cools not only the motor, but also the compressor and in particular
the cylinder heads, by means of targeted air cooling. The best possible
serviceability is provided by means of a replaceable drive motor, among other
things. The compressor stands out due to its outstanding running comfort and
efficient operating performance. Dependable mechanism lubrication is guaranteed
by means of an oil pump which is independent of rotating direction, as well as a
large-volume oil sump. An electronic motor protection uses PTC sensors in series
to monitor the winding temperature and, if desired, the discharge gas
temperature.
Colour: blue (RAL 5000)
Technical data
HAX12P/110-4
Application | Refrigeration & AC |
Compressor refrigeration capacity | 1.59 kW |
Power consumption | 1.30 kW |
Current draw (400 V) | 2.90 A |
Mass flow | 0.012 kg/s |
at following operating condition:
Refrigerant | R404A, R507 |
Reference temperature | Dew point |
Evaporating temperature | -35.0 °C |
Condensing temperature | 40.0 °C |
Supply frequency | 50 Hz |
Voltage | 400 V |
Suction gas temperature | 20 °C |
Subcooling (outside cond.) | 0 K |
Number of cylinders / Bore / Stroke | 2 / 45 mm / 34 mm |
Displacement 50/60 Hz (1450/1740 ¹/min) | 9,40 / 11,30 m³/h |
Voltage 1) | 220-240V Δ / 380-420V Y -3- 50Hz |
| 265-290V Δ / 440-480V Y -3- 60Hz |
Max. working current 2) | 7.0 / 4.1 A |
Max. power consumption 2) | 2.2 kW |
Starting current (rotor blocked) 2) | 43.0 / 25.0 A |
Motor protection | INT69 G |
Protection terminal box / HA-fan | IP 66 / IP 44 |
Voltage HA-fan | 230 V - 1 - 50/60 Hz, 40 W |
Weight | 53 kg |
Max. permissible overpressure (g) (LP/HP) 3) | 19 / 28 bar |
Connection suction line SV | 12 mm - 1/2 " |
Connection discharge line DV | 12 mm - 1/2 " |
Lubrication | Oil pump |
Oil type R134a, R404A, R407A/C/F, R448A, R449A, R450A, R513A | BOCKlub E55 |
Oil type R22 | BOCKlub A46 |
Oil charge | 0,8 Ltr. |
Dimensions
Length / Width / Height | 440 / 220 / 315 mm |
Scope of supply
Semi-hermetic two cylinder reciprocating compressor with
drive motor
Single-section compressor housing with hermetically integrated
electric motor
Winding protection with PTC resistor sensors and
electronic trigger unit INT69 G
115-230 V AC, 50/60 Hz,
IP00
Oil pump
Motor is cooled by an integrated ventilator with air
deflection hood.
230 V - 1 - 50/60 Hz, 40 W, 0,3 A
Possibility of
connection of oil level controllers ESK, Traxoil, AC+R or CARLY 4)
Oil charge:
HA: BOCKlub A46
HAX:
BOCKlub E55
Sight glass
Suction and discharge line valve
Inert gas charge
4 anti-vibration pads enclosed
Accessories
Oil sump heater
110-240 V - 1 - 50/60 Hz, 50-120 W, IP66
PTC heater
self-regulating
Oil pressure safety switch MP55 230 V - 1 - 50/60 Hz,
IP20 5)
Thermal protection thermostat per cylinder cover
6)
Special voltage and/or frequency (on request)
Notes
1) | Tolerance (± 10%)
relates to the mean value of the voltage range. Other voltages and current types
on request
All data are based on voltage rms values |
2) | - The stated value for the max. power consumption is valid
for the adjusted power supply.
- Starting current (rotor blocked):
- Part winding (PW) motors: Winding 1 / Winding 1+2
- Delta/Star (Δ/Y) motors: Δ / Y
- Take account of the max.
operating current / max. power consumption for designing motor contractors, feed
lines, fuses and motor protection switches. Motor contractors: Consumption
category AC3. |
3) | LP = Low
pressure HP = High pressure |
4) | Only with additional
adapter possible |
5) | Enclosure |
6) | Mounted |