Technical data
HGX2/110-4 CO2 T
Application | Refrigeration & AC |
Compressor refrigeration capacity | 20.10 kW |
Power consumption | 11.80 kW |
Current draw (400 V) | 22.50 A |
Mass flow | 0.133 kg/s |
at following operating condition:
Refrigerant | R744 |
Reference temperature | Dew point |
Evaporating temperature | -10.0 °C |
High pressure (abs.) | 90.00 bar |
Gas cooler outlet temperature | 35.0 °C |
Supply frequency | 50 Hz |
Voltage | 400 V |
Suction gas superheat | 10 K |
Subcooling (outside cond.) | -- K |
Number of cylinders / Bore / Stroke | 2 / 38 mm / 49 mm |
Displacement 50/60 Hz (1450/1740 ¹/min) | 9,70 / 11,60 m³/h |
Voltage 1) | 380-420V Y/YY -3- 50Hz PW |
| 440-480V Y/YY -3- 60Hz PW |
Winding divided into | 66% / 33% |
Max. working current 2) | 30.9 A |
Max. power consumption 2) | 17.6 kW |
Starting current (rotor blocked) 2) | 107.0 / 140.0 A |
Motor protection | MP10 |
Protection terminal box | IP 65 |
Weight | 160 kg |
Max. permissible overpressure (g) (LP/HP) 3) | 100 / 150 bar |
Connection suction line SV | 22 mm |
Connection discharge line DV | 18 |
Lubrication | Oil pump |
Oil type R744 | BOCKlub E85 |
Oil charge | 2,5 Ltr. |
Dimensions
Length / Width / Height | 635 / 320 / 415 mm |
Scope of supply
Semi-hermetic two cylinder reciprocating compressor with
drive motor in - 4-pole design
Single-part compressor housing
Oil pump
Winding protection with PTC resistor sensors and
electronic trigger unit MP 10
Oil sump heater 230 V - 1 - 50/60 Hz, 160 W
Oil charge:
BOCKlub E85
Sight glass
Pressure relief valve for HP and LP side
Inert gas charge
4 anti-vibration pads enclosed
Accessories
Compressor oil BOCKlub E85 as 1 liter refill
unit 4)
Thermal protection thermostat per cylinder cover
Suction and discharge line valve with cutting ring
connection for steel pipes
Special voltage and/or frequency (on request)
Notes
1) | Tolerance (± 10%)
relates to the mean value of the voltage range. Other voltages and current types
on request
All data are based on voltage rms values |
2) | - The stated value for the max. power consumption is valid
for the adjusted power supply.
- Starting current (rotor blocked):
- Part winding (PW) motors: Winding 1 / Winding 1+2
- Delta/Star (Δ/Y) motors: Δ / Y
- Take account of the max.
operating current / max. power consumption for designing motor contractors, feed
lines, fuses and motor protection switches. Motor contractors: Consumption
category AC3. |
3) | LP = Low
pressure HP = High pressure |
4) | Enclosure |