Technical data
HGX4/555-4 CO2
Application | Refrigeration & AC |
Compressor refrigeration capacity | 83.60 kW |
Power consumption | 21.50 kW |
Current draw (400 V) | 37.50 A |
Mass flow | 0.323 kg/s |
at following operating condition:
Refrigerant | R744 |
Reference temperature | Dew point |
Evaporating temperature | -35.0 °C |
Condensing temperature | -5.0 °C |
Supply frequency | 50 Hz |
Voltage | 400 V |
Suction gas superheat | 10 K |
Subcooling (outside cond.) | 0 K |
Number of cylinders / Bore / Stroke | 4 / 60 mm / 49 mm |
Displacement 50/60 Hz (1450/1740 ¹/min) | 48,20 / 57,80 m³/h |
Voltage 1) | 380-420V Y/YY -3- 50Hz PW |
| 440-480V Y/YY -3- 60Hz PW |
Winding divided into | 66% / 33% |
Max. working current 2) | 38.2 A |
Max. power consumption 2) | 22.0 kW |
Starting current (rotor blocked) 2) | 107.0 / 140.0 A |
Motor protection | INT69 G |
Protection terminal box | IP 65 |
Weight | 157 kg |
Max. permissible overpressure (g) (LP/HP) 3) | 27 / 55 bar |
Connection suction line SV | 35 mm - 1 3/8 " |
Connection discharge line DV | 28 mm - 1 1/8 " |
Lubrication | Oil pump |
Oil type R744 | BOCKlub E85 |
Oil charge | 2,7 Ltr. |
Oil sump heater | 230 V - 1 - 50/60 Hz, 80 W |
Dimensions
Length / Width / Height | 684 / 364 / 404 mm |
Scope of supply
Semi-hermetic four-cylinder reciprocating compressor with drive motor
Motor unit flanged onto the compressor housing
Winding protection with PTC resistor sensors and
electronic trigger unit INT69 G
115-230 V AC, 50/60 Hz,
IP00
Oil pump
Pressure relief valve suction and discharge line
Possibility of
connection of oil level controllers ESK, AC+R or CARLY
Oil pump cover with screw-in option for oil differential
pressure sensor DELTA-P II
Possibility of connection of oil level controllers Traxoil 4)
Oil charge:
BOCKlub E85
Sight glass
Suction and discharge line valve
Inert gas charge
4 anti-vibration pads enclosed
Accessories
Start unloader by means of a ESS (Electronic Soft
Start), 400 V - 3 - 50/60 Hz, IP20 (Connection clamps IP00) for installation in
switch cabinet 5)
Compressor oil BOCKlub E85 as 1 liter refill
unit 5)
Oil sump heater 230 V - 1 - 50/60 Hz, 80 W
Thermal protection thermostat
Oil service valve
Oil differential pressure sensor DELTA-P II 220-240 V -
1 - 50/60 Hz 5)
Water-cooled cylinder covers
Adapter for pressure relief valve 5)
Additional fan
230 V AC - 1 - 50 Hz, 97 W,
IP44
230 V AC - 1 - 60 Hz, 128 W 5)
Special voltage and/or frequency (on request)
Notes
1) | Tolerance (± 10%)
relates to the mean value of the voltage range. Other voltages and current types
on request
All data are based on voltage rms values
PW = part
winding, motors for part winding starting (no start unloaders required)
Designs for Y/D on request |
2) | - The stated value for the max. power consumption is valid
for the adjusted power supply.
- Starting current (rotor blocked):
- Part winding (PW) motors: Winding 1 / Winding 1+2
- Delta/Star (Δ/Y) motors: Δ / Y
- Take account of the max.
operating current / max. power consumption for designing motor contractors, feed
lines, fuses and motor protection switches. Motor contractors: Consumption
category AC3. |
3) | LP = Low
pressure HP = High pressure |
4) | Only with additional
adapter possible |
5) | Enclosure |