Technical data
HGX34P/215-4 CO2
Application | Refrigeration & AC |
Compressor refrigeration capacity | 33.10 kW |
Power consumption | 8.08 kW |
Current draw (400 V) | 13.60 A |
Mass flow | 0.128 kg/s |
at following operating condition:
Refrigerant | R744 |
Reference temperature | Dew point |
Evaporating temperature | -35.0 °C |
Condensing temperature | -5.0 °C |
Supply frequency | 50 Hz |
Voltage | 400 V |
Suction gas superheat | 10 K |
Subcooling (outside cond.) | 0 K |
Number of cylinders / Bore / Stroke | 4 / 41,5 mm / 40 mm |
Displacement 50/60 Hz (1450/1740 ¹/min) | 18,80 / 22,60 m³/h |
Voltage 1) | 220-240V Δ / 380-420V Y -3- 50Hz |
| 265-290V Δ / 440-480V Y -3- 60Hz |
Max. working current 2) | 29.7 / 17.2 A |
Max. power consumption 2) | 10.5 kW |
Starting current (rotor blocked) 2) | 132.0 / 76.0 A |
Motor protection | MP10 |
Protection terminal box | IP 66 |
Weight | 98 kg |
Max. permissible overpressure (g) (LP/HP) 3) | 40 / 55 bar |
Connection suction line SV | 22 mm - 7/8 " |
Connection discharge line DV | 16 mm - 5/8 " |
Lubrication | Oil pump |
Oil type R744 | BOCKlub E85 |
Oil charge | 1,3 Ltr. |
Dimensions
Length / Width / Height | 510 / 280 / 315 mm |
Scope of supply
Semi-hermetic four
cylinder reciprocating compressor with drive motor
Single-section compressor housing with hermetically integrated electric
motor
Oil pump
Winding protection with PTC resistor sensors and
electronic trigger unit MP 10
Possibility of
connection of oil level controllers ESK, Traxoil, AC+R or CARLY 4)
Oil charge:
BOCKlub E85
Sight glass
Pressure relief valve for HP and LP side
Suction and discharge line valve
Inert gas charge
4 anti-vibration pads enclosed
Accessories
Start unloader by means of a ESS (Electronic Soft
Start), 400 V - 3 - 50/60 Hz, IP20 (Connection clamps IP00) for installation in
switch cabinet 5)
Progressively adjustable speed control by means of an
EFC (Electronic Frequency Control),
compactly built onto compressor and
connected ready-to-operate
HA/HG12P: IP65
HA22P/HG22e, HA34P/HG34e: IP54
Compressor oil BOCKlub E85 as 1 liter refill
unit
Oil sump heater
110-240 V - 1 - 50/60 Hz, 50-120 W, IP66
PTC heater
self-regulating
Thermal protection thermostat
Additional fan
230 V AC - 1 - 50 Hz, 97 W,
IP44
230 V AC - 1 - 60 Hz, 128 W 5)
Special voltage and/or frequency (on request)
Notes
1) | Tolerance (± 10%)
relates to the mean value of the voltage range. Other voltages and current types
on request
All data are based on voltage rms values |
2) | - The stated value for the max. power consumption is valid
for the adjusted power supply.
- Starting current (rotor blocked):
- Part winding (PW) motors: Winding 1 / Winding 1+2
- Delta/Star (Δ/Y) motors: Δ / Y
- Take account of the max.
operating current / max. power consumption for designing motor contractors, feed
lines, fuses and motor protection switches. Motor contractors: Consumption
category AC3. |
3) | LP = Low
pressure HP = High pressure |
4) | Only with additional
adapter possible |
5) | Enclosure |