Technical data
HGX22e/85-4 S CO2
| Application | Refrigeration & AC |
| Compressor refrigeration capacity | 13.40 kW |
| Power consumption | 3.23 kW |
| Current draw (400 V) | 6.49 A |
| Mass flow | 0.052 kg/s |
at following operating condition:
| Refrigerant | R744 |
| Reference temperature | Dew point |
| Evaporating temperature | -35.0 °C |
| Condensing temperature | -5.0 °C |
| Supply frequency | 50 Hz |
| Voltage | 400 V |
| Suction gas superheat | 10 K |
| Subcooling (outside cond.) | 0 K |
| Number of cylinders / Bore / Stroke | 2 / 45 mm / 27 mm |
| Displacement 50/60 Hz (1450/1740 ¹/min) | 7,50 / 9,00 m³/h |
| Voltage 1) | 220-240V Δ / 380-420V Y -3- 50Hz |
| 265-290V Δ / 440-480V Y -3- 60Hz |
| Max. working current 2) | 15.6 / 9.0 A |
| Max. power consumption 2) | 5.2 kW |
| Starting current (rotor blocked) 2) | 111.0 / 64.0 A |
| Motor protection | INT69 G |
| Protection terminal box | IP 66 |
| Weight | 83 kg |
| Max. permissible overpressure (g) (LP/HP) 3) | 40 / 55 bar |
| Connection suction line SV | 22 mm - 7/8 " |
| Connection discharge line DV | 16 mm - 5/8 " |
| Lubrication | Oil pump |
| Oil type R744 | BOCKlub E85 |
| Oil charge | 1,0 Ltr. |
| Dimensions
Length / Width / Height | 505 / 240 / 330 mm |
Scope of supply
Semi-hermetic two cylinder reciprocating compressor with
drive motor
Single-section compressor housing with hermetically integrated
electric motor
Winding protection with PTC resistor sensors and
electronic trigger unit INT69 G
115-230 V AC, 50/60 Hz,
IP00
Oil pump
Pressure relief valve suction and discharge line
Possibility of
connection of oil level controllers ESK, Traxoil, AC+R or CARLY 4)
Oil charge:
BOCKlub E85
Sight glass
Suction and discharge line valve
Inert gas charge
4 anti-vibration pads enclosed
Accessories
Start unloader by means of a ESS (Electronic Soft
Start), 400 V - 3 - 50/60 Hz, IP20 (Connection clamps IP00) for installation in
switch cabinet 5)
Compressor oil BOCKlub E85 as 1 liter refill
unit
Oil sump heater
110-240 V - 1 - 50/60 Hz, 50-120 W, IP66
PTC heater
self-regulating
Thermal protection thermostat
Adapter for pressure relief valve
Additional fan
230 V AC - 1 - 50 Hz, 97 W,
IP44
230 V AC - 1 - 60 Hz, 128 W 5)
Special voltage and/or frequency (on request)
Notes
| 1) | Tolerance (± 10%)
relates to the mean value of the voltage range. Other voltages and current types
on request
All data are based on voltage rms values |
| 2) | - The stated value for the max. power consumption is valid
for the adjusted power supply.
- Starting current (rotor blocked):
- Part winding (PW) motors: Winding 1 / Winding 1+2
- Delta/Star (Δ/Y) motors: Δ / Y
- Take account of the max.
operating current / max. power consumption for designing motor contractors, feed
lines, fuses and motor protection switches. Motor contractors: Consumption
category AC3. |
| 3) | LP = Low
pressure HP = High pressure |
| 4) | Only with additional
adapter possible |
| 5) | Enclosure |