Technical data
EX-HGX34P/215-4 S
Application | Refrigeration & AC |
Compressor refrigeration capacity | 9.54 kW |
Power consumption | 3.03 kW |
Current draw (400 V) | 6.93 A |
Mass flow | 0.067 kg/s |
at following operating condition:
Refrigerant | R134a |
Reference temperature | Dew point |
Evaporating temperature | 5.0 °C |
Condensing temperature | 50.0 °C |
Supply frequency | 50 Hz |
Voltage | 400 V |
Suction gas temperature | 20 °C |
Subcooling (outside cond.) | 0 K |
Number of cylinders / Bore / Stroke | 4 / 41,5 mm / 40 mm |
Displacement 50/60 Hz (1450/1740 ¹/min) | 18,80 / 22,60 m³/h |
Voltage 1) | 380-420V Y -3- 50Hz |
| 440-480V Y -3- 60Hz |
Max. working current 2) | 10.5 A |
Max. power consumption 2) | 6.0 kW |
Starting current (rotor blocked) 2) | 76.0 A |
Motor protection | MP10 |
Protection terminal box | IP 65 |
Weight | 96 kg |
Max. permissible overpressure (g) (LP/HP) 3) | 19 / 28 bar |
Connection suction line SV | 22 mm - 7/8 " |
Connection discharge line DV | 16 mm - 5/8 " |
Lubrication | Oil pump |
Oil type R134a, R404A, R407A/C/F, R448A, R449A, R450A, R513A | BOCKlub E55 |
Oil type R22 | BOCKlub A46 |
Oil type R290, R1270 | BOCKlub G68 |
Oil charge | 1,3 Ltr. |
Dimensions
Length / Width / Height | 510 / 285 / 355 mm |
Scope of supply
Semi-hermetic four
cylinder reciprocating compressor with drive motor
Single-section compressor housing
with hermetically integrated electric motor
Oil pump
Winding protection with PTC resistor sensors. Electronic
triggering unit MP 10 to be fitted in switch cupboard (enclosed)
2-channel safety barrier as energy limiting device in
self secure circuit in order to prevent firing through sparks or thermic
effects,
for fitting into switch cabinet (enclosed)
Possibility of
connection of oil level controllers ESK, Traxoil, AC+R or CARLY 4)
Oil charge:
HG: FUCHS Reniso SP 46
HGX: FUCHS Reniso Triton SE
55
HG HC: FUCHS Reniso SYNTH 68
Sight glass
Pressure relief valve
Suction and discharge line valve
Thermal protective thermostat for each cylinder
head
Inert gas charge
4 anti-vibration pads enclosed
Accessories
Capacity regulator 230 V - 1 - 50/60 Hz, IP66
1
capacity regulator = 50% residual capacity,
explosion-proof, equipment
category 2 as per directive 2014/34/EU
Oil sump heater 230 V - 1 - 50/60 Hz, 80
W,
explosion-proof, equipment category 2 as per directive 2014/34/EU
(enclosure) 5)
Special painting Offshore (Compressor with insulating
surface coating)
Special voltage and/or frequency (on request)
No further
accessories possible
Notes
1) | Tolerance (± 10%)
relates to the mean value of the voltage range. Other voltages and current types
on request
All data are based on voltage rms values |
2) | - The stated value for the max. power consumption is valid
for the adjusted power supply.
- Starting current (rotor blocked):
- Part winding (PW) motors: Winding 1 / Winding 1+2
- Delta/Star (Δ/Y) motors: Δ / Y
- Take account of the max.
operating current / max. power consumption for designing motor contractors, feed
lines, fuses and motor protection switches. Motor contractors: Consumption
category AC3. |
3) | LP = Low
pressure HP = High pressure |
4) | The operation of this components is only allowed with a
suitable protection class. Only with additional adapter possible.
|
5) | Enclosure |