HGX12

Types HP (motor code) 1) kW 2) Displacement at 50 Hz (1450 rpm) m³/h
HGX12/20-4 S CO2 T 3 4 1.7
HGX12/30-4 S CO2 T 4 4 2.8
HGX12/40-4 S CO2 T 5 4 3.5

HG CO2 T compressors, transcritical

The compressors are used for transcritical and subcritical applications in supermarkets, commercial and industrial plants, and heat pumps.

• Gas-cooled, semi-hermetic reciprocating compressors
• Operating pressures of up to 130 bar
• Conceived for transcritical CO2-systems:
   Standstill pressures LP 100 bar / HP 150 bar
• Highest compressor and system efficiency through specific CO2 design with lowest oil carry over

Special features
• Highest compressor efficiency for lowest operating costs
• Long-life compressor design
• Reliable and safe oil supply through pump lubrication
• Low oil throw-off
• Good operating characteristics with low vibration, low pulsation, and low operating noise
• Broad limits of application and large frequency range for a wide variety of uses
• Pressure relief valves for the suction and pressure area
• Long experience with transcritical CO2 compressors (since 1993)

Important information
• CO2 applications require a new kind of system and control
• They do not represent a general solution for substitution of F-gases
• The notes on handling CO2 compressors in the instructions for assembly must be followed
• We specifically point out that all information in this brochure is based on our current level of knowledge and may change at any time due to further development


1)
The motor code describes the compressor motor size based on the HP (Horse Power) of the compressor that is usual in refrigeration technology worldwide. However, the motor code does not correspond to the converted nominal power of the motor from [kW] to [HP].

2)
Nominal power of the motor in [kW].